| Plan Review Notes For Permit 14030310 |
| Permit Number |
14030310 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-11 17:09:20 | 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) A SEPARATE APPLICATION, PERMIT AND REVIEW IS | | | REQUIRED FOR ELECTRICAL. CITY AMENDMENTS 105.1 | | | | | | 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE | | | LOCATIONS OF ALL ELECTRICAL RECPTACLES, SWITCHES AND | | | LIGHTING OUTLETS IN THE AREAS AFFECTED BY THE ADDITIONS | | | OF THE HALF BATH AND THE TWO BEDROOM CLOSETS. SHOW | | | COMPLIANCE WITH NEC 210,52 REQUIRED RECEPTACLE OUTLETS, | | | NEC 210.70 LIGHTING OUTLETS REQUIRED, NEC 210.17 | | | 9(C)(3) BRANCH CIRCUITS REQUIRED, SHOW LOCATION OF THE | | | ELECTRICAL METER AND PANEL. | | | | | | 3) THE ADDRESS OF THE JOB, THE NAME SIGNATURE AND | | | LISENCE NUMBER OF THE PERSON RESPONSIBLE FOR THE | | | ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY | | | AMENDMENTS 107 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|