Plan Review Notes
Plan Review Notes For Permit 14030310
Permit Number 14030310
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-11 17:09:202008 NEC
  
 DENIED BY ELECTRICAL
  
 1) A SEPARATE APPLICATION, PERMIT AND REVIEW IS
 REQUIRED FOR ELECTRICAL. CITY AMENDMENTS 105.1
  
 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATIONS OF ALL ELECTRICAL RECPTACLES, SWITCHES AND
 LIGHTING OUTLETS IN THE AREAS AFFECTED BY THE ADDITIONS
 OF THE HALF BATH AND THE TWO BEDROOM CLOSETS. SHOW
 COMPLIANCE WITH NEC 210,52 REQUIRED RECEPTACLE OUTLETS,
 NEC 210.70 LIGHTING OUTLETS REQUIRED, NEC 210.17
 9(C)(3) BRANCH CIRCUITS REQUIRED, SHOW LOCATION OF THE
 ELECTRICAL METER AND PANEL.
  
 3) THE ADDRESS OF THE JOB, THE NAME SIGNATURE AND
 LISENCE NUMBER OF THE PERSON RESPONSIBLE FOR THE
 ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107
  