| Plan Review Notes For Permit 14030309 |
| Permit Number |
14030309 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-22 10:39:18 | NO ELECTRICAL SHEET OR SPECS OF ANY KIND WERE SUBMITTED | | | FOR APPROVAL. BELOW IS A COPY OF THE NOTES FROM THE | | | PREVIOUS REVIEW WHICH HAS BEEN IGNORED. | | | | | | ELECTRICAL REVIEW WAS DENIED DUE TO THE FOLLOWING: | | | 1.ELECTRICAL DRAWINGS COMPLYING WITH ALL OF THE | | | REQUIREMENTS OF THE NEC SHALL BE SUBMITTED FOR REVIEW | | | AND ACCEPTANCE. | | | THE NEC HAS SPECIFIC OUTLET, SWITCHING AND LIGHTING | | | PLACEMENT REQUIREMENTS THAT HAVE TO BE COMPLIED WITH. | | | THERE ARE SPECIFIC REQUIREMENTS ASSOCIATED WITH THE SPA | | | AS WELL THAT COME INTO PLAY AND SHALL BE ADDRESSED. | | | LITERATURE ON THE PROPOSED SPA SHALL ACCOMPANY THE | | | SUBMITTAL. | | | NEC 680.43(B) HAS LIMITATIONS ON THE CEILING FAN ABOVE | | | THE SPA. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] |
|