| Plan Review Notes For Permit 14030190 |
| Permit Number |
14030190 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-13 15:00:35 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW | | | EXTERIOR DOORS AND WINDOWS AS REQUIRED BY DCA RULE | | | 9N-3. | | | | | | 2) SHOW COMPLIANCE WITH FBC R301.2.1.2, WHICH REQUIRES | | | LARGE MISSILE PROTECTION FOR GLAZED OPENINGS THAT ARE | | | PART OF THE BUILDING ENVELOPE. IF STORM PANELS WILL BE | | | INSTALLED, SUBMIT TWO COPIES OF PRODUCT APPROVALS, AN | | | INSTALLATION SCHEDULE AND A KEY PLAN. | | | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED BY BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 107.3.4.1 | | | | | | 4) TO HELP SPEED THE REVIEW PROCESS, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH REVIEW COMMENT HAS | | | BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|