| Date |
Text |
| 2014-09-27 15:44:29 | ****PROVISO**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | PROJECT: LOFTIN PLACE |
| | CONTRACTOR CONTACT: [email protected] , |
| | ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL, |
| | [email protected] |
| | ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R. |
| | MIDDLEBROOKS PE [email protected] |
| | CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES: |
| | [email protected] 561-856-6655 |
| | |
| | GENERAL COMMENT: IN THE CASE OF REDLINES, PLEASE |
| | INCORPORATE INTO ARCHITECT'S SHEETS AS APPLICABLE. |
| | THESE REDLINED/REVISED SHEETS DO NOT NEED TO BE |
| | SUBMITTED UNLESS REQUESTED IN THE PROVISO OR UNLESS THE |
| | SHEET IS REVISED IN THE FUTURE. IF THE SHEET CHANGES |
| | DUE TO ANOTHER REVIEWER'S COMMENT, PLEASE INCORPORATE |
| | REDLINES/NOTES. |
| | |
| | PROVISO - SEPARATE PERMIT REQUIRED FOR SIGNAGE, AWNINGS |
| | |
| | PROVISO - PRODUCT APPROVALS FOR COMPONENTS AND CLADDING |
| | WILL BE SUBMITTED AT A FUTURE DATE PRIOR TO |
| | INSTALLATION, NO FEE. THEY ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | PROVISO - PRODUCT DATA TEST REPORTS REVIEWED BY |
| | DESIGNER OF RECORD FOR FLOORING ACOUSTIC INSULATION |
| | WILL BE PROVIDED AT A FUTURE DATE PRIOR TO |
| | INSTALLATION, NO FEE (FBC 1207.2, 1207.3, 603.1 FLAME |
| | SPREAD LESS THAN 200) |
| | |
| | PROVISO - DUROLAST NOA PROVIDED. THE APPROVED ASSEMBLY |
| | PROPOSED AND RAS117 CALCULATIONS (IF REQUIRED) TO BE |
| | SUBMITTED WITH ROOF PERMIT. THIS IS TO BE REVIEWED BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | PREVIOUS COMMENTS WHICH ARE NOW PROVISO ITEMS: |
| | |
| | 6 & 8. SHEET SD1, THESE ITEMS (SEE COMMENT LIST #1) |
| | HAVE BEEN ADDED TO THE PLANS. INCORPORATE LANGUAGE INTO |
| | THE ARCHITECT'S SHEET IN THE EVENT THAT THIS SHEET IS |
| | REVISED IN THE FUTURE. IF ARCHITECT HAS AN OBJECTION TO |
| | THE ADDED TEXT, PLEASE CONTACT ME TO DISCUSS. |
| | |
| | 17. S1.8, ROOF DESIGN PRESSURES TREAT ZONE 3 AS ZONE 2. |
| | PLEASE SEE ASCE7010, FIGURE 30.6-1, FOOTNOTE , PARAPET |
| | TO BE EQUAL TO OR HIGHER THAN 3FT. DETAIL A A7.1 |
| | APPEARS TO SHOW A 2FT PARAPET AT STAIR 1, PLEASE |
| | CLARIFY OR INCLUDE ZONE 3 PRESSURES FOR ROOF CORNER |
| | ZONES LACKING A 3 FT PARAPET. REVISE ROOF PLAN TO |
| | CLARIFY WHERE HIGHER ZONE 3 DESIGN PRESSURES ARE |
| | REQUIRED. PRIOR TO ROOF PERMIT APPLICATION, THIS SHEET |
| | SHOULD EITHER BE REVISED OR REVISE DETAILS WHICH SHOW A |
| | 2 FT HIGH PARAPET. THIS IS TO BE SUBMITTED AS A |
| | REVISION PRIOR TO ROOF PERMIT APPLICATION. |
| | |
| | 33. EXITING FROM POOL THROUGH DOOR 138.11 APPEARS TO |
| | ALSO USE 138.9. GATES ARE TO MEET THE SAME REQUIREMENTS |
| | AS DOORS, FBC 1008.2. REVISE TO INCLUDE THE GATE |
| | INFORMATION FOR COMPONENTS SERVING IN THE MEANS OF |
| | EGRESS AROUND THE POOL AREA. PLAN HAS BEEN REDLINED; |
| | PLEASE INCORPORATE INTO ARCHITECT'S DRAWINGS. THIS |
| | SHEET IS NOT REQUIRED TO BE SUBMITTED AT THIS TIME. |
| | |