| 2014-08-29 07:18:42 | 705 NORTH OLIVE AVENUE |
| | PERMIT #14030096 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| | REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| | WITH FLORIDA AMENDMENTS.) |
| | |
| | |
| | ROUND #2 COMMENTS: |
| | |
| | SHEET C-06: DUE TO THE COMBINED SIZE OF THE STRUCTURES, |
| | PLEASE PROVIDE AN ADDITIONAL FIRE DEPARTMENT CONNECTION |
| | FRONTING A STREET OTHER THAN EUCALYPTUS STREET. |
| | |
| | SHEET LP 3.0: CABANAS, UMBRELLAS, TENTS, CURTAINS, |
| | DRAPES AND OTHER LOOSELY HANGING FINISHINGS/DECORATIONS |
| | SHALL MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701 |
| | (MATERIAL WILL SELF EXTINGUISH ONCE DIRECT FIRE FLAME |
| | HAS BEEN REMOVED). |
| | |
| | SHEET SD-1: PER SECTION 10.12.1.2 (NFPA 1), ADDRESS |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | SHEET A-0.1.1: PROVIDE BOLLARD BARRIERS OUTSIDE THE |
| | FIRE PUMP ROOM DOORS TO ENSURE THESE DOORS ARE NOT |
| | BLOCKED BY STORAGE, VEHICLES, ETC. |
| | |
| | SHEET A-01.1: THE MAIN ENTRY EXTERIOR AREA ADJACENT TO |
| | STAIR #4 HAS 4 EXIT DOORS DISCHARGING INTO THIS AREA |
| | AND A SINGLE EXIT DISCHARGE DOOR LEADING TO OLIVE |
| | AVENUE. IS THE EXIT WIDTH OF THE SINGLE DOOR SUFFICIENT |
| | TO HANDLE THE OCCUPANT LOAD? |
| | |
| | SHEET A-0.1.1 & A-5.1.1: ONLY 1 EXIT SIGN PROVIDED IN |
| | YOGA ROOM #CH101. THE NEXT CLOSEST EXIT SIGN IS RIGHT |
| | OUTSIDE EXIT ACCESS DOOR #CH101B AND THIS EXIT SIGN |
| | LEADS TO A DISCHARGE RIGHT NEXT TO THE OTHER EXIT DOOR |
| | (#CH101A). NO SECOND EXIT SIGN IN THE FITNESS GYM OR |
| | CIRULAR ROTUNDA AREA. NO EXIT SIGN IN CONFERENCE ROOM |
| | #CH106 OR LEASING #107A. |
| | |
| | SHEET A-0.1.1: COULD NOT LOCATE ANY FIRE RATED GLAZING |
| | IN WINDOW OR DOOR SCHEDULES. FOR EXAMPLE, PARKING |
| | GARAGE MAIL ROOM SHOWS GLAZING, IN A FIRE RATED WALL. |
| | ALSO SHEET A-5.1.6 AND SHEET A-2.1.7 INDICATE A |
| | 45-MINUTE FIRE RATED DOOR (DOOR TYPE C) WITH 1/4" |
| | TEMPERED GLASS. |
| | |
| | GENERAL: THE ARCHITECTURAL LIFE SAFETY PLANS EXIT |
| | SIGNAGE AND THE ELECTRICAL PLANS EXIT SIGNAGE NEED TO |
| | BE COORDINATED ALL SHEETS. |
| | |
| | SHEET A-0.1: COULD NOT LOCATE A DOOR SCHEDULE FOR THE |
| | AMENITY LEASING OFFICE AREAS. COULD NOT LOCATE INTERIOR |
| | DESIGN SHEETS (ID SERIES) IN THIS SUBMITTAL. DRAWING |
| | INDEX INDICATES A DOOR SCHEDULE ON SHEETS ID9.04 AND |
| | ID9.05 WHICH COULD NOT BE FOUND. |
| | |
| | SHEET A-0.1.2: SEVERAL AREAS IN THE AMENITIES/LEASING |
| | OFFICE ARE OPEN TO THE FLOOR BELOW. THE DESIGN SHALL |
| | CONFORM TO SECTION 8.6 VERTICAL OPENINGS AS EITHER A |
| | COMMUNICATING SPACE, CONVENIENCE OPENING, ATRIUM, OR |
| | MEZZANINE. FOR INSTANCE, EACH OCCUPANT NOT IN THE |
| | COMMUNICATING SPACE (SUCH AS AMENITY SECOND FLOOR REST |
| | ROOM) NEEDS TO HAVE ACCESS TO AT LEAST ONE EXIT WITHOUT |
| | HAVING TO ENTER THE COMMUNICATING SPACE, OR AS A |
| | CONVENIENCE OPENING, THE OPENINGS NEED TO BE SEPARATED |
| | FROM CORRIDORS. |
| | |
| | SHEET A-01.4: A CALCULATED OCCUPANT LOAD OF 26 PERSONS |
| | GROSSLY UNDERESTIMATES THE POTENTIAL FOR PERSONS TO |
| | UTILIZE THIS LARGE AMOUNT OF SPACE AS AN ASSEMBLY USE. |
| | ORIGINAL COMMENT: PROVIDE AN ASSEMBLY OCCUPANCY |
| | OCCUPANT LOAD FOR THE ROOFTOP RECREATIONAL DECK |
| | FEATURING THE TENNIS COURT, WALKING COURSE, AND SUN |
| | DECK AREAS. |
| | |
| | GENERAL: ARE ALL STAIRWAY DOORS TO REMAIN UNLOCKED AT |
| | ALL TIMES FROM THE STAIRWELL SIDE OR WILL THERE BE |
| | DESIGNATED RE-ENTRY FLOORS? |
| | |
| | SHEET A-5.1.6: ALL FIRE RATED DOORS SHALL BE AUTOMATIC |
| | CLOSING OR SELF CLOSING AND POSITIVE LATCHING. SEVERAL |
| | DOORS DO NOT INDICATE THIS SUCH AS DOOR #756.1, 756.2 |
| | ETC. |
| | |
| | ELECTRICAL: THE COLORING AND LINE WEIGHTS IN THE |
| | DIGITAL PLANS MAKE IT EXTREMELY DIFFICULT TO VERIFY |
| | WHICH FIXTURES ARE REPRESENTING THE EMERGENCY LIGHTING |
| | PARTICULARLY ON THE FIRST FLOOR AND IN THE PARKING |
| | GARAGE. PLEASE CLEARLY DISTINGUISH. |
| | |
| | SHEET E-2.1.1: WHY HAS THE EXIT SIGN BEEN REMOVED IN |
| | CORRIDOR FOR STAIR #4? APPEARS ARCHITECTURAL FLOOR PLAN |
| | IS DIFFERENT THAN THE FLOOR PLAN FOR THIS SHEET. |
| | |
| | SHEET E-2.1.1: COULD NOT LOCATE ANY ILLUMINATED EXIT |
| | SIGNS AND EMERGENCY LIGHTING FOR THE AREA. |
| | |
| | SHEET E-2.1.7: THIS FLOOR PLAN APPEARS TO BE DIFFERENT |
| | THAN THE ARCHITECTURAL FLOOR PLAN WHICH DOES NOT SHOW |
| | ACCESS TO THE NORTHWEST STAIRS FROM THE TENNIS COURT |
| | AREA. |
| | |
| | SHEET E-2.1.7 PROVIDE NORMAL AND EMERGENCY LIGHTING FOR |
| | ROOFTOP AREQS SUCH AS RUNNING TRACK, SUNDECK, ETC. |
| | |
| | SHEET E-4.4: THE FLOOR PLAN APPEARS TO BE THE OLD |
| | ARCHITECTURAL FLOOR PLAN WITH THE SPIRAL STAIR. |
| | |
| | SHEET FP-2.1.1: DO NOT ROUTE THE FDC LINE THROUGH THE |
| | TRASH ROOM. THESE TYPES OF ROOMS HAVE AN INCREASED FIRE |
| | HAZARD AND CAN HAVE CORROSIVE ATMOSPHERES. THE PIPING |
| | IS ALSO ROUTED OUTSIDE OF THE BUILDING ADJACENT TO |
| | STAIR #5. |
| | |
| | SHEET FA 2.1.1.: REFER TO NFPA 101 SECTION 12.3.4.3.3 |
| | FOR REQUIRED VOICE ANNOUNCEMENTS. |
| | ORIGINAL COMMENT - FA: NEED VOICE EVAC FIRE ALARM |
| | SYSTEM FOR ASSEMBLY AREA AS OCCUPANT LOAD EXCEEDS 300 |
| | PERSONS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | WEST PALM BEACH FIRE RESCUE |