| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | SHEET E-7.1.1; E-7.1.2 |
| | PROVIDE MAIN BREAKERS FOR MC #3, MC # 6 AND MC# 7. NEC |
| | 240.21 |
| | |
| | SHEET E-6.1.1 |
| | PROVIDE CLARIFICATION REGARDING THE SELECTION AND TYPE |
| | OF GROUND FAULT PROTECTION PROPOSED FOR THE SERVICE |
| | EQUIPMENT. NEC 230.95 |
| | |
| | SHEET E-5.1.1; E-5.1.2; E-5.1.3; E-5.1.4 |
| | VERIFY THAT ALL DOORS TO THE ELECTRICAL EQUIPMENT ROOMS |
| | ARE EQUIPPED WITH PANIC HARDWARE. |
| | NEC 110.26 C (3) |
| | |
| | SHEET E-5.1.2 |
| | SUFFICIENT ACCESS AND WORKING SPACE HAS NOT BEEN |
| | PROVIDED FOR THE THIRD LEVEL METER ROOM. NEC 110.26 |
| | |
| | SHEET E- 6.1.1 |
| | THE ELECTRICAL POWER SOURCE FOR THE FIRE PUMP REQUIRES |
| | A SEPARATE AND RELIABLE POWER SOURCE. NEC 695.3 |
| | CIRCUITS THAT SUPPLY ELECTRIC MOTOR-DRIVEN FIRE PUPS |
| | SHALL BE SUPERVISED FROM INADVERTENT DISCONNECTION. NEC |
| | 695.4 |
| | THE DISCONNECTION MEANS FOR THE FIRE PUMP SHALL NOT BE |
| | LOCATED WITHIN EQUIPMENT THAT FEEDS LOADS OTHER THAN |
| | THE FIRE PUMP. NEC 695.4 |
| | VERIFY THE FIRE PUMP OVER CURRENT DEVICE WILL CARRY |
| | INDEFINITELY THE LOCKED-ROTOR CURRENT, THE CONDUCTORS |
| | HAVE A RATING OF NOT LESS THAN 125 PERCENT OF THE LOADS |
| | AND THE VOLTAGE DROP AT THE CONTROLLER IS WITHIN AN |
| | ACCEPTABLE RANGE. NEC 695.6, 695.7 |
| | VERIFY THE FIRE PUMP CONDUCTORS ARE KEPT INDEPENDENT OF |
| | ALL OTHER WIRING AND ARE FIRE PROTECTED. NEC 695.6 |
| | PROVIDE SPECIFICATIONS ON THE FIRE PUMP CONTROLLER. NEC |
| | 695.4(B)(2), 90.7 |
| | PROVIDE FIRE PUMP DISCONNECT AND CONTROLLER MARKINGS. |
| | NEC 695.4(B)(3) AND (4). |
| | |
| | |