| 2014-05-23 16:35:21 | 1. COLUMNS ON GARAGE VEHICULAR ACEESS ENCROACH INTO THE |
| | SETBACK. |
| | 2. GROSS AREA INDICATED ON SHEET SD-1 IS 192,065SF |
| | WHILE SP-1.1 INDICATED 272,963SF. PLEASE CLARIFY |
| | DIFFERENCE. SITE PLAN APPROVAL DRAWINGS INDICATE |
| | 274,976SF. |
| | 3.DRAWINGS SEEM TO INDICATE AN ADDITIONAL UNIT ADDED ON |
| | THE TOP FLOOR ON THE WEST SIDE OF THE PARKING GARAGE. |
| | PLEASE EXPLAIN IF THAT IS THE CASE, AND INDICATE THE |
| | INCREASE IN SQUARE FOOTAGE. |
| | 4.PLEASE INCLUDE A COMPLETE GROSS BUILDING AREA, AND |
| | OPEN SPACE REQUIREMENT CALCULATION TABLE AS INCLUDED IN |
| | THE SITE PLAN APPROVAL DRAWINGS. |
| | 5. PLEASE INDICATE THE MECHANICAL SCREENING FOR ALL |
| | ROOF TOP EQUIPMENT. PARAPET WALL SHALL BE AS HIGH AS |
| | THE MECHANICAL EQUIPMENT. |
| | 6. PLEASE SPECIFY THAT THE TREE GRATE SHALL MATCH |
| | EXISTING ON OLIVE AND DIXIE AVENUE. |
| | 7. STREET LIGHT SHALL MATCH EXISTING ON OLIVE AND DIXIE |
| | HWAY. |
| | 8. BIKE RACK SPECIFIED ON DETAILS INCLUDES TWO ANCHORS. |
| | PLEASE INDICATE THE TWO ANCHORS IN THE OVERALL DRAWINGS |
| | OR INCLUDE A SPECIFIC INSTALLATION DETAIL IDENTIFYING |
| | MINIMUM DISTANCES TO COMPLY WITH BIKE RACK INSTALLATION |
| | STANDARDS. |
| | 9. ARE THE BIKE RACKS PROPOSED INSIDE THE PARKING |
| | GARAGE THE SAME MODEL THAN THE ONES OUTSIDE BY THE |
| | PLAZA? PLEASE SPECIFY IF DIFERENT. |
| | 10. IT SEEMS THERE IS A UTILITY LINE RUNNING UNDER THE |
| | MIDDLE OF THE TREE GRATES ON OLIVE AVE. PLEASE CONFIRM |
| | THAT IS NOT THE CASE OR RELOCATE. |
| | 11. SWITCH BOXES SHALL INCLUDE A SCREEN FILM IF |
| | LANDSCPE IS NOT POSSIBLE FOR SCREENING. |
| | 12. SIDEWALK ON SOUTH SIDE OF EUCALYPTUS SHALL BE |
| | COMPLETED FROM THE PHASE I TO DIXIE HWAY, OR AT LEAST |
| | CONNECTED WITH THE EXISTING SIDEWALK TO ALLOW |
| | PEDESTRIAN TRAFFIC ALONG THE ENTIRE FRONTAGE. |
| | 13. HAVE THE TOTAL NUMBER OF TREES BEING MODIFIED SINCE |
| | THE SITE PLAN APPROVAL? OVERALL DRAWIGNS DO NOT SEEM TO |
| | HAVE THE SAME NUMBER THAN THE DETAIL DRAWINGS. |
| | 14. STRUCTURAL SOITL SHALL BE SPECIFIED UNDER THE |
| | SIDEWALK 10' AROUND THE TREE TRUNK. PHOTOS OF THE |
| | STRUCTURAL SOIL INSTALLATION SHALL BE SUBMITTED AS PART |
| | OF THE CO PROCESS. |
| | 15. IF THE ROOF TOP IS COUNTED AS PART OF THE PRIVATE |
| | OPEN SPACE, PLEASE PROVIDE INFORMATION TO CONFIRM |
| | COMPLIANCE WITH LANDSCAPE ROOF TOP REQUIREMENTS. |
| | 16. AS THE PUBLIC OPEN SPACE IS PROPOSED ALL UNDER THE |
| | PHASE I, IT SHALL BE BUILT IN ITS ENTIRETY DURING THIS |
| | PHASE. |
| | 17. MAIN BUILDING ENTRANCE WAS MODIFIED FROM THE DIXIE |
| | FRONTAGE TO THE 6TH STREET FRONTAGE. HOWEVER, BUILDING |
| | DESIGN STILL SEEMS TO DIRECT PEDESTRIANS TO THE DIXIE |
| | ENTRANCE DUE TO THE ARCHITECTURAL FEATURE ON THE |
| | BUILDING. SOME ADDITIONAL FEATURE SHALL BE ADDED UNDER |
| | THAT COVERED ENTRANCE (FOUNTAIN?) AND THE NEW MAIN |
| | ENTRANCE SHALL BE ENHANCED TO CREATE A NEW ENTRY |
| | FEATURE ON THE NEW LOCATION. |
| | 18. WHAT ARE THE NEW VERTICAL LINES SHOWN ON THE 6TH |
| | STREET ELEVATION WEST OF THE STAIR AND EAST OF THE |
| | PARKIGN ENTRANCE? |
| | 19. IS THERE ANY CHANGE ON THE SIDEWALK ELEVATION EAST |
| | AND WEST OF THE PARKING ENTRANCE? |
| | 20. PLEASE INCLUDE DIMENSIONS FOR ALL PARKING STALLS |
| | WITHIN THE GARAGE. |
| | 21. BALCONIES CANNOT ENCROACH MORE THAN 5 FEET INTO |
| | MINIMUM SETBACK. PLEASE CONFIRM COMPLIANCE. |
| | 22. BAND THAT SEPARATED BASE FROM MIDDLE AT THE N SIDE |
| | OF THE OLIVE ELEVATION IS MISSING SHEET A-3.1.1 |
| | 23. NEW DOORS ON SIDES OF LOADING ARE NOT ACCURATELY |
| | REFLECTED ON ELEVATION. FACADE SHALL BE ADJUSTED TO |
| | REFLECT THE NEW ELEMENTS. |
| | 24. BUILDING NAME IS NOT ALLOWED AS A MONUMENT SIGN, IT |
| | SHALL BE LOCATED ON THE BUILDING FACADE. |
| | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA |
| | APONTE AT 561-822-1439. |
| | |