| 2014-05-03 11:29:37 | PLUMBING PLAN REVIEW |
| | LOFTIN PLACE |
| | PERMIT: 14030096 |
| | ADD: 705 N OLIVE AVE |
| | CONT: KAST CONSTRUCTION |
| | TEL: (561)689-2910 |
| | CONTACT: NEYITA (561)856-6655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 03/2014 |
| | ACTION: DENIED |
| | |
| | 632 DRAWING SHEETS ARE IN THIS ELECTRONIC SET OF PLANS |
| | AND ARE LISTED 1-632. |
| | |
| | 1) MISSING PLUMBING SHEETS FROM THE INDEX AND THE |
| | PLUMBING SHEETS THAT ARE FOUND IN THE FOUNDATION |
| | PERMIT. |
| | 1A) THE INDEX INDICATES SHEET P-1.1.1 SITE PLAN SHOULD |
| | BE IN THIS SET OF DRAWINGS. ELECTRONIC SHEET 460. |
| | |
| | 1B) INDEX NOT SHOWING THESE SHEETS NOR THE ELECTRONIC |
| | SHEETS MISSING NUMBERED 461, 462 & 463 ARE NOT FOUND IN |
| | THIS SET. THIS IS A COMPLETE PLUMBING PLAN REVIEW OF |
| | THE BUILDING TO FOLLOW THROUGH WITH THE MINIMUM |
| | PLUMBING PLAN REVIEW FOR THE FOLLOWING SYSTEMS: |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION107.3.5.1.3. PLUMBING |
| | MINIMUM PLUMBING PLAN REVIEW: |
| | SANITARY DRAINAGE MISSING PLUMBING FOUNDATION SHEETS |
| | NOT COMPLETE |
| | ROOF DRAINAGE MISSING PLUMBING FOUNDATION SHEETS |
| | BACK FLOW PREVENTION 2010 FBC-PLUMBING 608.1. |
| | IRRIGATION PLANS / BACKFLOW DEVICES/ RAIN SENSOR |
| | CONTROLLERS F. S. 373.82 |
| | LOCATION OF PLUMBING SUPPLY LINES 2010 FBC-PLUMBING |
| | 603.2 CAN NOT BE VARIFIED |
| | |
| | 2) SHEET P-2.1.1A PARTIAL SHEET OF GROUND FLOOR NOT |
| | INDEX GRID LINES MISSING TO IDENTIFY LOCATIONS. |
| | |
| | 2A) THIS SHEET ALSO INDICATES THE USE OF A SAND FILTER |
| | IN THE 8 INCH GARAGE DRAIN LINE, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION TO THE LOCATION OF THE SAND |
| | FILTER AND MANUFACTURERS SPECIFICATION. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. PLANS INDICATE SEE |
| | CIVIL DRAWINGS WHERE PLEASE? |
| | |
| | 2B) ROOMS ARE NOT IDENTIFIED, I BELIEVE THE 2 ROOMS |
| | WITH 6 INCH FLOOR DRAINS ARE THE PUMP ROOM AND THE |
| | TRASH COLLECTION/ TERMINATION ROOM A 4 INCH & THREE |
| | INCH FLOOR DRAIN. THE FLOOR DRAIN SYSBOL IS NOT FOUND |
| | ON THE PIPING SYMBOLS P-6.1 SHEET, IT IS HARD TO |
| | DETERMINE IF THEY HAVE TRAPS OR NOT, BUT THEY DO NOT |
| | INDICATE THE USE OF A TRAP PRIMER REQUIRED BY 2010 |
| | FBC-P 1002.1 FIXTURE TRAPS. |
| | |
| | 2B)(1) THE DRAIN SCHEDULE FOUND ON P-6.1 DEALS WITH |
| | TRAPS , ONE * (STAR) & ***THREE (STARS) DEAL WITH TRAPS |
| | WITH MOVING PARTS (BALL-FLOAT ADOPTER) PLEASE REVIEW P- |
| | 1002.3 PROHIBITED TRAPS. |
| | THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS |
| | THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL. |
| | |
| | 2B)(2) DEFINE A DEEP TRAP SEAL (SHOWN AS **** 4 STARS) |
| | MECHANICAL EQUIPMENT AT ROOF. THIS TERM IS NOT IN THE |
| | 2010 FBC-PLUMBING CODE. |
| | M] 314.2.4 TRAPS. CONDENSATE DRAINS SHALL BE TRAPPED AS |
| | REQUIRED BY THE EQUIPMENT OR APPLIANCE MANUFACTURER. |
| | |
| | 2C) THE 6 INCH SANITARY LOCATED IN THE N.E. PORTION OF |
| | THE BILDING DOES NOT IDENTY THE TRANSITION TO 8 INCH |
| | EXCEPT WHEN IT LEAVES THE BUILDING. 2010 FBC-P TABLE |
| | 710.1(1) PROVIDE SLOPE PER FOOT DETERMINES DFU COUNT. |
| | |
| | 2D) THIS COMMENT IS FOR ALL FLOORS. PLEASE PLACE A PIPE |
| | LEGEND ON EACH FLOOR LAYOUT SHEET AS TO WHAT CIRCLES,& |
| | DIAMONDS REPRESENT, 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIED. REVIEWS CAN NOT BE COMPLETED AT THIS TIME |
| | WITHOUT IDENTIFICATION. |
| | |
| | 3A) SHEET P-2.19 ROOF DECK AND THE TOP GARAGE PARKING |
| | DECK DO NOT PROVIDE THE CALCULATIONS SHOWING |
| | CONTRIBUTING PARAPET WALLS, THE |
| | PLANS DO NOT PROVIDE AS TO WHAT RAINFALL THEIR DESIGN |
| | IS FIGURED FOR UNDER THE 100 -YEAR HOURLY RAINFALL |
| | BASED. SEE 2010 FBC-P SECTION 1106.1 AND FIGURE 1106.1. |
| | |
| | 3B) ROOF AND THE TOP GARAGE DECK TO PROVIDE IN THE |
| | CALCULATIONS SQUARE FOOTAGE FOR VERTICAL WALLS IN |
| | ACCORDANCE WITH THE 2010 FBC-PLUMBING 1106.4. |
| | 1101.3 PROHIBITED DRAINAGE. |
| | STORM WATER SHALL NOT BE DRAINED INTO SEWERS INTENDED |
| | FOR SEWAGE ONLY. |
| | 1101.4 TESTS. |
| | THE CONDUCTORS AND THE BUILDING STORM DRAIN SHALL BE |
| | TESTED IN ACCORDANCE WITH SECTION 312. |
| | 1101.5 CHANGE IN SIZE. |
| | THE SIZE OF A DRAINAGE PIPE SHALL NOT BE REDUCED IN THE |
| | DIRECTION OF FLOW. |
| | 1101.6 FITTINGS AND CONNECTIONS. |
| | ALL CONNECTIONS AND CHANGES IN DIRECTION OF THE STORM |
| | DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED |
| | DRAINAGE-TYPE FITTINGS IN ACCORDANCE WITH TABLE 706.3. |
| | THE FITTINGS SHALL NOT OBSTRUCT OR RETARD FLOW IN THE |
| | SYSTEM. |
| | 1101.8 CLEANOUTS REQUIRED. |
| | CLEANOUTS SHALL BE INSTALLED IN THE STORM DRAINAGE |
| | SYSTEM AND SHALL COMPLY WITH THE PROVISIONS OF THIS |
| | CODE FOR SANITARY DRAINAGE PIPE CLEANOUTS. |
| | |
| | 3C) IDENTIFY THE MATERIALS TO BE USED FOR THE |
| | INSTALATION OF STORM WATER PIPING, SHOW COMPLIANCE |
| | WITH: |
| | 1102.1 GENERAL. |
| | THE MATERIALS AND METHODS UTILIZED FOR THE CONSTRUCTION |
| | AND INSTALLATION OF STORM DRAINAGE SYSTEMS SHALL COMPLY |
| | WITH THIS SECTION AND THE APPLICABLE PROVISIONS OF |
| | CHAPTER 7. |
| | 1102.2 INSIDE STORM DRAINAGE CONDUCTORS. |
| | INSIDE STORM DRAINAGE CONDUCTORS INSTALLED ABOVE GROUND |
| | SHALL CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE |
| | 702.1. |
| | 1102.3 UNDERGROUND BUILDING STORM DRAIN PIPE. |
| | UNDERGROUND BUILDING STORM DRAIN PIPE SHALL CONFORM TO |
| | ONE OF THE STANDARDS LISTED IN TABLE 702.2. |
| | 1102.4 BUILDING STORM SEWER PIPE. |
| | BUILDING STORM SEWER PIPE SHALL CONFORM TO ONE OF THE |
| | STANDARDS LISTED IN TABLE 1102.4. |
| | |
| | 4) PLANS FAIL TO PROVIDE DETAILS FOR BOTH FL. |
| | ACCESSIBILITY CODE PART A IF THERE ARE BUSINESS |
| | OFFICES, RETAIL STORES, ETC AND PART II FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES. |
| | |
| | 2010 FBC-ACCESSIBILITY CODE 101.1.3 THIS CODE |
| | ESTABLISHES STANDARDS FOR ACCESSIBILITY TO PLACES OF |
| | PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES BY |
| | INDIVIDUALS WITH DISABILITIES. THIS CODE SHALL ALSO |
| | APPLY: TO STATE AND LOCAL GOVERNMENT FACILITIES |
| | PURSUANT TO SECTION 553.503, F.S.; TO PRIVATE CLUBS |
| | PURSUANT TO SECTION 553.505, F.S.; AND TO RESIDENTIAL |
| | BUILDINGS PURSUANT TO SECTION 553.504(2), F.S., AND THE |
| | ADA STANDARDS FOR ACCESSIBLE DESIGN. IT IS TO BE |
| | APPLIED DURING THE DESIGN CONSTRUCTION AND ALTERATION |
| | OF SUCH BUILDINGS AND FACILITIES AS REQUIRED BY THIS |
| | CODE. |
| | |
| | FAIR HOUSING ACCESSIBILITY GUIDELINES SCOPE |
| | THESE GUIDELINES APPLY ONLY TO THE DESIGN AND |
| | CONSTRUCTION REQUIREMENTS OF 24 CFR 100.205. COMPLIANCE |
| | WITH THESE GUIDELINES DO NOT RELIEVE PERSONS |
| | PARTICIPATING IN A FEDERAL OR FEDERALLY-ASSISTED |
| | PROGRAM OR ACTIVITY FROM OTHER REQUIREMENTS, SUCH AS |
| | THOSE REQUIRED BY SECTION 504 OF THE REHABILITATION ACT |
| | OF 1973 (29 U.S.C. 794) AND THE ARCHITECTURAL BARRIERS |
| | ACT OF 1968 (42 U.S.C. 4151-4157). ACCESSIBLE DESIGN |
| | REQUIREMENTS FOR SECTION 504 ARE FOUND AT CFR PART 8. |
| | ACCESSIBLE DESIGN REQUIREMENTS FOR THE ARCHITECTURAL |
| | BARRIERS ACT ARE FOUND AT 24 CFR PART 40. |
| | PURPOSE |
| | THE PURPOSE OF THESE GUIDELINES IS TO PROVIDE TECHNICAL |
| | GUIDANCE ON DESIGNING DWELLING UNITS AS REQUIRED BY THE |
| | FAIR HOUSING AMENDMENTS ACT OF 1988 (FAIR HOUSING ACT). |
| | THESE GUIDELINES ARE NOT MANDATORY, NOR DO THEY |
| | PRESCRIBE SPECIFIC REQUIREMENTS WHICH MUST BE MET, AND |
| | WHICH, IF NOT MET, WOULD CONSTITUTE UNLAWFUL |
| | DISCRIMINATION UNDER THE FAIR HOUSING ACT. BUILDERS AND |
| | DEVELOPERS MAY CHOOSE TO DEPART FROM THESE GUIDELINES |
| | AND SEEK ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE |
| | MET THE REQUIREMENTS OF THE FAIR HOUSING ACT. THESE |
| | GUIDELINES ARE INTENDED TO PROVIDE A SAFE HARBOR FOR |
| | COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF THE |
| | FAIR HOUSING ACT.SECTION 4. APPLICATION OF THE |
| | GUIDELINES |
| | REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| | USE AREAS. |
| | REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS. |
| | REQUIREMENT 7 - USABLE KITCHENS AND BATHROOMS. |
| | |
| | 5) NOTE NO ACTION NEEDS TO BE TAKEN, NOTICE! |
| | SHEET P-6.1 THE PLUMBING FIXTURE CONNECTION SCHEDULE |
| | PLEASE NOTE THE SHOWER IS LISTED WITH A 1 1/2 INCH TRAP |
| | & 2 INCH WASTE THAT IS CODE COMMPLIANT WHEN USED WITH A |
| | SHOWER BASED ON THE TOTAL FLOW RATE THROUGH SHOWER |
| | HEADS AND BODY SPRAYS OF 5.7 GPM OR LESS. |
| | |
| | 6) SHEET P-6.1 DETAILS A TRASH CHUTE WITH A FLUSHING |
| | SPRAY RING AT THE TOP OF THE ROOM OPERTED BY A SOLENOID |
| | AND SWITCH IN THE TRASH ROOM. |
| | PLEASE PROVIDE THE MANUFACTURERS SPEC ON THIS DEVICE, |
| | LISTED FOR SUCH AN APPLICATION. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | PLEASE NOTE THIS DEVICE WILL NOT EXEMPT THE REQUIREMENT |
| | FOR FIRE SPRINKLERS FOUND UNDER THE 2010 FBC-B |
| | 903.11.2. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |