| 2014-04-30 09:34:24 | PLAN DENIED |
| | APARTMENTS |
| | 1) PROVIDE DUCT SIZE GOING TO 36X6 GRILL |
| | 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S |
| | 2010 FBC (M) |
| | PROVIDE A DOOR SCHEDULE ON THE PLAN NEED TO KNOW WHAT |
| | TYPE OF |
| | DOOR IS GOING ON AIR HANDLER CLOSET, IF THE CLOSET IS A |
| | RETURN AIR |
| | PLENUM. |
| | 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION |
| | 2010 FBC (M) |
| | |
| | ROOF |
| | 1) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M) |
| | PROVIDE ENGINEER DETAIL ON A/C STANDS. HOW THE STANDS |
| | ARE |
| | TIED TO THE ROOF, AND HOW CONDENSERS ARE TIED TO THE |
| | STANDS. |
| | 2) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M) |
| | PROVIDE A DETAIL FROM THE ENGINEER FOR THE CURB TO ROOF |
| | TIE DOWN |
| | AND RTU TIE DOWN TO CURB. |
| | 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS. |
| | FLORIDA ENERGY CODE 2010. |
| | |
| | LEASING OFFICE |
| | 1) REFER TO SECTION 401.5 INTAKE OPENING PROTECTION. |
| | 2010 FBC (M). |
| | 2) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION |
| | 2010 FBC (M) |
| | 3) REFER TO SECTION 602.2.1 METERIALS WITHIN PLENUM'S. |
| | 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS |
| | FLORIDA ENERGY CODE. |
| | 5) REFER TO SECTION 601.4 BALANCED RETURN AIE 2010 |
| | FBC (M) |
| | 6) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEN.2010 FBC |
| | (M) |
| | 7) REFER TO SECTION 606.3 INSTALLATION. 2010 FBC (M) |
| | 8) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M) |
| | 9) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING AND |
| | COOLING |
| | LOADS. 2010 FLORIDA ENERGY CODE. |
| | |
| | PLAN REVIEW BY HAROLD MOSER |