Text |
| 2014-03-06 10:39:37 | 2500 METROCENTRE BOULEVARD W - #1 | | | PERMIT #14030076 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER SECTION NFPA 101 SECTION 8.3.2.4, EACH FIRE BARRIER | | | SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS. | | | CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND | | | HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT | | | MORE THAN 15 FEET ON CENTER. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|