 REVIEW COMMENTS- FIRE DEPARTMENT
  
 THE SPRINKLER RISERS/CONTROL VALVES NEED TO BE LOCATED
 OUTSIDE OF THE BUILDINGS OR PREFERABLY IN A DEDICATED
 RISER ROOM WITH ACCESS FROM THE EXTERIOR OF THE
 BUILDING DUE TO THE SPRINKLER RISERS PROTECTING
 MULTIPLE TENANT SPACES.
  
 THE SPRINKLER RISERS AND FDC CONNECTIONS SHALL BE
 PROVIDED WITH PERMANENT WEATHERPROOF SIGNAGE INDICATING
 WHICH BUILDING THEY ARE PROTECTING.
  
 PROVIDE LOCKING KNOX CAPS ON THE FIRE DEPARTMENT
 CONNECTIONS.
  
 MINIMUM 1-INCH OUTLETS SHALL BE PROVIDED ON BRANCH
 LINES TO ACCOMMODATE TENANT FITOUTS THAT MAY UTILIZE
 LAY-IN CEILINGS.
  
 SUBMIT SPRINKLER CUT SHEET INFORMATION. ALL SPRINKLERS
 IN THE SPRINKLER SCHEDULE APPEAR TO BE ONLY LISTED FOR
 LIGHT HAZARD OCCUPANCIES WITH THE EXCEPTION OF RELIABLE
 MODEL G XLO (STORAGE SPRINKLER).
  
 THE RELIABLE MODEL G XLO IS INDICATED AS A QUICK
 RESPONSE SPRINKLER IN THE SCHEDULE; HOWEVER, I BELIEVE
 THIS IS A STANDARD RESPONSE TYPE.
  
 TENANT B14 INDICATES THE USAGE OF STORAGE SPRINKLER
 RELIABLE G XLO. PLEASE INDICATE THE NFPA 13 DESIGN
 SECTION OR DESIGN TABLE THAT THIS DESIGN IS IN
 COMPLIANCE WITH. INDICATE THE MAXIMUM STORAGE HEIGHT,
 COMMODITY CLASSIFICATION, RACK STORAGE (OR PALLETIZED,
 SOLID, ETC.) AND AISLE CONFIGURATION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WPB FIRE RESCUE