Plan Review Notes
Plan Review Notes For Permit 14021098
Permit Number 14021098
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-03-06 08:19:34THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH COMMENTS
 BY PETER LEDUC, FIRE MARSHAL, BUREAU OF FIRE
 PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. THE FIRE ALARM SYSTEM SHALL BE MAINTAINED AND ACTIVE
 DURING CONSTRUCTION.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP
 DRAWING COMPLIANT WITH NFPA 72 IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 3. ANY TIME WORK IS DONE ON THE FIRE ALARM SYSTEM, AND
 IT IS TURNED OFF EXCEEDING 4 HOURS, A FIRE WATCH SHALL
 BE IMPLEMENTED AND MAINTAINED UNTIL FULL AND COMPLETE
 PROTECTION IS RETURNED.
  
 4. ALL EXITS SHALL BE MAINTAINED CLEAR AND FREE DURING
 CONSTRUCTION FOR THE SAFE EXIT OF ALL OCCUPANTS.