Plan Review Notes
Plan Review Notes For Permit 14021098
Permit Number 14021098
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-20 13:25:1814021098
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE FEEDER SIZE FOR THE NEW PANEL ?LP?-B?. NEC
 215.5
  
 INDICATE ON THE PLAN THAT THE LIGHTING SYSTEM AND
 LIGHTING DENSITIES COMPLY WITH THE FLORIDA BUILDING
 ENERGY CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 THE WATER FOUNTAIN REQUIRES A BRANCH CIRCUIT AND GFCI
 PROTECTION. NEC 422.52
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  