| Plan Review Notes For Permit 14021098 |
| Permit Number |
14021098 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-20 13:25:18 | 14021098 | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE THE FEEDER SIZE FOR THE NEW PANEL ?LP?-B?. NEC | | | 215.5 | | | | | | INDICATE ON THE PLAN THAT THE LIGHTING SYSTEM AND | | | LIGHTING DENSITIES COMPLY WITH THE FLORIDA BUILDING | | | ENERGY CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | THE WATER FOUNTAIN REQUIRES A BRANCH CIRCUIT AND GFCI | | | PROTECTION. NEC 422.52 | | | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINK MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|