| 2014-03-10 10:46:20 | BUILDING PLAN REVIEW |
| | PERMIT: 14021098 |
| | ADD: 915 S DIXIE HWY |
| | CONT: DEALERSHIP SOLUTIONS, LLC |
| | TEL: (727)894-2150 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY, MARCH 10/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A001 INDICATE THREE (3) PRODUCT |
| | APPROVALS FOR NEW GLAZING UNITS, PLEASE PROVIDE 2 |
| | COPIES OF PRODUCT APPROVALS REQUIRED BY RULE 9N-03. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | PLEASE IDENTIFY THE GLAZING, TYPES, SIZE, ASSOCIATED |
| | PRESSURES, MULLIONS SIZE IF REINFORECED OR NOT, |
| | LIMITATIONS AND PRESSURES. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, PLEASE PROVIDE THE MANUFACTURERS |
| | PRODUCT APPROVAL AS WELL AS INSTALATION INSTRUCTIONS |
| | FOR THE EFIS WALL SYSTEMS AND ASSOCIATED PRESSURES AND |
| | LIMITATIONS SEE 2010 FBC-B 1408.5 INSTALATION. |
| | |
| | |
| | |
| | 3A) THE PLANS SHOW EXISTING ELEMENTS THAT ARE NOT IN |
| | COMPLIANCE WITH THE 2010 FL ACCESSIBILITY CODE, THE |
| | 2010 FL EISTING BUILDING CODE LEVEL II ALTERATIONS. |
| | 706.1 GENERAL. A BUILDING, FACILITY, OR ELEMENT THAT IS |
| | ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | 2010 FL ACCESSIBILITY CODE 202.4 ALTERATIONS AFFECTING |
| | PRIMARY FUNCTION AREAS. |
| | IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION |
| | THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS |
| | TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE |
| | SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, |
| | THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE |
| | REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING |
| | THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE |
| | BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH |
| | ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL |
| | ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1. |
| | ALTERATIONS TO WINDOWS, HARDWARE, CONTROLS, ELECTRICAL |
| | OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED TO BE |
| | ALTERATIONS THAT AFFECT THE USABILITY OF OR ACCESS TO |
| | AN AREA CONTAINING A PRIMARY FUNCTION. |
| | 202.4.1 DISPROPORTIONATE COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | PLEASE PROVIDE A COST ANALYSIS WHERE DISPROPORTIONALITY |
| | WILL BE MET. PLEASE REVIEW 202.4 WHICH COST THAT CAN BE |
| | DEDUCTED FROM THE CONTRACT VALUE ( . ALTERATIONS TO |
| | WINDOWS, HARDWARE, CONTROLS, ELECTRICAL OUTLETS, AND |
| | SIGNAGE) THE CURRENT PERMIT VALUATION STANDS AT |
| | $627,500,00. THE 20% DISPROPORTIONE COST WOULD BE |
| | $125,500.00 THIS NUMBER WILL BE REDUCED WITH THE ABOVE |
| | MENTIONED COST BROKE OUT OF THE VALUE OF THE PROJECT. |
| | THE REMAINDER OF THESE FEES WILL NEED TO BE SPENT TO |
| | BRING THE BUILDING UP TO THE 2010 FL ACCESSIBILITY |
| | STANDARDS. |
| | |
| | 3B) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3B)(1) SHEET A402 DETAIL # C1. ROOM 107.1 INDICATES A |
| | NEW EMPLYEE BREAK ROOM AREA (KEYED CONTROL AREA) PLEASE |
| | BROVIDE COMPLIANCE WITH 2010 FL ACCESS. 606.2 CLEAR |
| | FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 606.4 FAUCETS. |
| | CONTROLS FOR FAUCETS SHALL COMPLY WITH 309. |
| | HAND-OPERATED METERING FAUCETS SHALL REMAIN OPEN FOR 10 |
| | SECONDS MINIMUM. |
| | |
| | 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE |
| | SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | 3B)(2) SHEET A402 DETAIL # C1 INDICATES THE HEIGHT OF |
| | ONLY ONE DRINKING FOUNTAIN WHEREAS SHEET A101 SHOWS A |
| | HIGH LOW FOUNTAIN IN COMPLIANCE WITH 2010 FL |
| | ACCESSIBILITY CODE 211 REQUIRING A MINIMUM OF 2 A HIGH |
| | & LOW. |
| | |
| | 3C)(1) SHEET A402 DETAIL # A1 DOES NOT PROVIDE THE |
| | HEIGHT OF THE COUNTER TOP FL ACCESS. CODE 606.3 606.3 |
| | HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND, NOR |
| | DOES SHEET A101 SHOW COMPLIANCE WITH FL ACCESS CODE |
| | 606.2 CLEAR FLOOR SPACE, 606.4 FAUCET OR 606.5 EXPOSED |
| | PIPES. |
| | |
| | 4) THIS BUILDING IS BEING DECLARED AS A IIB BUILDING |
| | SHEET S401 DETAIL D1 SHOWS ACONCRETE PIER ON EXISTING |
| | PILE CAP WITH ONLY A 2" CLEARANCE ABOVE GRADE TO TOP OF |
| | THE NEW FOUNDATION WITH EFIS WALL FINISH ABOVE. IS THIS |
| | BUILDING TRUELY A IIB MEETING THE EXCEPTION NOT |
| | REQUIRING A 6 INCH CLEARANCE FROM GRADE TO WHERE THE |
| | EFIS BEGINS? 2603.8 FBC-B. |
| | |
| | 5A) SHEET A101 NOTE # 7 INDICATES THE USE OF DORMA |
| | FRAMELESS SLIDING DOOR SYSTEM, PLEASE PROVIDE |
| | MANUFACTURERS SPEC ON THIS SYSTEM, THE OCCUPANT LOAD IN |
| | THESE AREAS WILL BE UNDER 10 AND WILL COMPLY WITH |
| | EGRESS REQUIREMENTS BUT HOW DOES IT COMPLY WITH THE |
| | REQUIREMENTS FOR 2010 FL ACCESS CODE 404.2 & 404.2.7 |
| | DOOR HARDWARE. |
| | |
| | SHEET A102 NOTE # 3 ALSO INDICATES THE USE OF TEKNION |
| | SLIDING GLASS DOORS, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FL ACCESS CODE 404.2 & 404.2.7 DOOR HARDWARE. |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |