| 2014-12-11 18:20:38 | 2010 FBC | | | 3RD REVIEW | | | DENIED BY BUILDING | | | | | | 1) THE INFORMATION LISTED ON THE ENERGY CALCULATION IS | | | NOT CONSISTANT WITH THE EQUIPMENT SIZING CALCULATIONS | | | OR THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS. THE | | | SEER AND BTUS FOR THE HEATING AND COOLING ARE | | | DIFFERENT. PLEASE CORRECT. THE INFORMATION ON THE PLANS | | | AND ENERGY FORMS ARE REQUIRED TO BE CONSISTENT. FBC | | | R107.2.1 | | | | | | 2) THE PREPARER AND THE OWNER/AGENT ARE REQUIRED TO | | | SIGN THE ENERGY CALC. FORM. FBC ENERGY CONSERVATION | | | SECTION 103.2.3.2 | | | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | | PGT IMPACT RATED SINGLE HUNG WINDOWS THAT ARE SPECIFIED | | | ON PLAN SHEET A102 AS REQUIRED BY DCA RULE 9N-3. | | | MIAMI-DADE NOAS AND FLORIDA PRODUCT APPROVALS ARE | | | ACCEPTABLE. | | | | | | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 107.3.4.1 | | | | | | 5) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A | | | RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW | | | COMMENTS WAS ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|