| Plan Review Notes For Permit 14021097 |
| Permit Number |
14021097 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-30 09:10:06 | 2010 FBC | | | | | | DENIED BY MECHANICAL (2ND REVIEW) ( ITEMS 2 THROUGH 5 | | | FROM THE FIRST REVIEW WERE NOT ADDRESSED.) | | | | | | 1) COMPLIED | | | | | | 2) SPECIFY THE SIZE OF THE RETURN AIR TRANSFER DUCTS TO | | | SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED RETURN | | | AIR. | | | | | | 3) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE NEW | | | BATHROOM. CITY AMENDMENTS 107.3.5.3 | | | | | | 4) THE BATHROOM EXHAUST DUCTS ARE REQUIRED TO DISCHARGE | | | DIRECTLY TO THE OUTDOORS. FBCR M1507.2 | | | | | | 5) INDICATE HOW THE RETURN AIR WILL GET TO THE AIR | | | HANDLER THAT IS LOCATED IN THE CLOSET. IF IT IS THROUGH | | | THE BI-FOLD DOORS, SPECIFY THAT THEY WILL BE LOUVERED. | | | FBCR M1602 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|