Plan Review Notes
Plan Review Notes For Permit 14021097
Permit Number 14021097
Review Stop M
Sequence Number 2
Notes
Date Text
2014-10-30 09:10:062010 FBC
  
 DENIED BY MECHANICAL (2ND REVIEW) ( ITEMS 2 THROUGH 5
 FROM THE FIRST REVIEW WERE NOT ADDRESSED.)
  
 1) COMPLIED
  
 2) SPECIFY THE SIZE OF THE RETURN AIR TRANSFER DUCTS TO
 SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED RETURN
 AIR.
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE NEW
 BATHROOM. CITY AMENDMENTS 107.3.5.3
  
 4) THE BATHROOM EXHAUST DUCTS ARE REQUIRED TO DISCHARGE
 DIRECTLY TO THE OUTDOORS. FBCR M1507.2
  
 5) INDICATE HOW THE RETURN AIR WILL GET TO THE AIR
 HANDLER THAT IS LOCATED IN THE CLOSET. IF IT IS THROUGH
 THE BI-FOLD DOORS, SPECIFY THAT THEY WILL BE LOUVERED.
 FBCR M1602
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]