| 2014-07-16 15:47:33 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS |
| | STRUCTURE IS LOCATED IN 17O MPH VULT WIND SPEED AND |
| | EXPOSURE CATEGORY C. THE FBCR 301.2.1 |
| | |
| | 2) PROVIDE A STRUCTURAL DETAIL FOR THE CONCRETE BLOCK |
| | WALL IN-FILL AT THE KITCHEN WINDOW THAT SHOWS THE |
| | REINFORCING BAR SIZE AND LOCATION. CITY AMENDMENTS |
| | 107.2.1.3 & FBCR 301.1 |
| | |
| | 3) THE TYPE OF CONSTRUCTION FOR THIS STRUCTURE IS V-B |
| | PER FBC TABLE 601. PLEASE CORRECT BUILDING TYPE ON |
| | SHEET A100. |
| | |
| | 4) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS |
| | AND FBCR 315 FOR CARBON MONOXIDE ALARMS. |
| | |
| | 5) SHOW THAT THE BATHROOM WINDOWS COMPLY WITH FBCR |
| | 308.4 FOR SAFETY GLAZING IN HAZARDOUS LOCATIONS. |
| | |
| | 6) THE WINDOW BUCK DETAIL ON SHEET A102 SPECIFIES 3/13" |
| | X 1-3/4" TAPCONS WITH A 1-1/4" MINIMUM WOOD EMBED. THE |
| | EXTERIOR WALLS ARE CONCRETE BLOCK NOT WOOD. THE LENGTH |
| | OF THE TAPCONS WILL NOT PROVIDE AN 1-1/4" EMBED DEPTH |
| | WHEN FASTENED THROUGH A 3/4" BUCK AND A 1/4" SHIM |
| | SPACE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBCR |
| | 612.10.2.1 |
| | |
| | 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA |
| | BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS |
| | LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION |
| | NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION |
| | SECTION 103.2.1.1.1 |
| | |
| | 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. |
| | FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2 |
| | |
| | 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE |
| | ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6. |
| | PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION |
| | 103.2.3.2 |
| | |
| | 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR |
| | CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A |
| | WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT |
| | WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY |
| | CONSERVATION SECTION 103.2.1.1.1 |
| | |
| | 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT |
| | & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN |
| | SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED |
| | BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT |
| | APPROVALS ARE ACCEPTABLE. |
| | |
| | 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. CITY AMENDMENTS 107.3.4.1 |
| | |
| | 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING |
| | PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS |
| | ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS, |
| | AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3 |
| | & CITY AMENDMENTS 107.2.1. |
| | |
| | 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A |
| | RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW |
| | COMMENTS WAS ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |