| Plan Review Notes For Permit 14021084 |
| Permit Number |
14021084 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-03 13:24:18 | RESIDENTIAL (R2) ALTERATION LEVEL 1, BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE THE FOLLOWING FOR THE SOUND INSULATION | | | UNDERLAYMENT TO BE USED: | | | | | | A) PROVIDE MANUFACTURER'S SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE FLAME SPREAD INDEX AND SMOKE | | | DEVELOPED INDEX IN ACCORDANCE WITH ASTM E84 OR UL 723 | | | AS REQUIRED BY SEC. 719.1 OF 2010 FBC. | | | | | | B) PROVIDE MANUFACTURER'S SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE AIR BORNE SOUND TRANSMISSION TEST | | | (ASTM E 90) AS REQUIRED BY SEC. 1207.2 OF 2010 FBC. | | | | | | C) PROVIDE MANUFACTURER'S SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE STRUCTURE-BORNE SOUND IMPACT | | | INSULATION TEST (ASTM E 492) AS REQUIRED BY SEC. 1207.3 | | | OF 2010 FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PANS EXAMINER | | | (561)805-6712 |
|