Notes
Date Text
2014-03-11 18:39:42AS PER THE FBC-B SECTION 907.1.2 YOUR DRAWINGS ARE
 MISSING:
 1. THE LOCATION OF THE PRIMARY POWER SOURCE, WITH THE
 SPECIAL PROTECTION CHARACTERISTICS OF THE NEC & NFPA 72
 2. YOU SHALL PROVIDE A LIST OF CONDUCTOR TYPES AND
 SIZES
 3. VOLTAGE DROP CALCULATIONS
 4. CLASSIFY THE SUPERVISING STATION
 SUBMIT A SEQUENCE OF OPERATION.