| Plan Review Notes For Permit 14021056 |
| Permit Number |
14021056 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-28 11:52:35 | PLUMBING PLAN REVIEW | | | REVISION: 14021056 | | | PERMIT: 13010504 | | | ADD: 631 EVERNIA ST | | | CONT: KAUFMAN LYNN CONSTREUCTION | | | TEL: (561)827-2078 MATHEW HURLEY | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: FRIDAY FEB. 28/ 2014 | | | | | | ACTION: PASSED/ PROVISO | | | | | | 1) THIS REVISION IS PASSED, PROVISO THAT THE LATICRETE | | | PRODUCT HYDRO BAN BE INSTALLED WITHIN THE LIMITATIONS | | | FOUND IN THE ERS-2417 REPORT AND THE MANUFACTURER'S | | | LIMITATIONS & GUIDELINES DS663.5 . APPLICATION IS | | | LIMITED TO CERAMIC TILE AND DIMENSION STONE | | | INSTALLATION ON CONCRETE FLOORS, USE AS SHOWER LINING, | | | OR OVER SURFACE CRACKS OR JOINTS UP TO 1/8 INCH | | | HORIZNTAL MOVEMENT AND NO VERTICAL DIFFERENTIAL | | | MOVEMENT. | | | | | | 2) IF SPRAY APPLICATION IS TO BE APPLIED, ALL | | | INSTALLATION AND SURFACE PREPERATION REQUIREMENTS | | | OUTLINED WITHIN THE MANUFACTURERS DOCUMENTS DS663.5 & | | | TSD 410. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|