| Plan Review Notes For Permit 14021002 |
| Permit Number |
14021002 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-03-10 12:15:46 | THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE PLANS | | | FOR APPROVAL. | | | 1. INDICATE WHERE THE EMERGENCY CUT-OFF SWITCH REQUIRED | | | BY NEC 514.11 IS LOCATED. | | | 2. INDICATE ON THE PLANS THE LOCATION OF THE TWO | | | DISPENSERS MENTIONED ON THE NOTES AND NOT SHOWN ON THE | | | PLANS. | | | 3. INDICATE THE SCOPE OF WORK ON THE PLANS, IF YOU ARE | | | ONLY REPLACING OLD, DAMAGED OR DEFECTIVE DEVICES WITH | | | NEW ONES IN THE SAME LOCATIONS, STATE SO. IF YOU ARE | | | ADDING ANY NEW ITEMS, PLEASE INDICATE. |
|