| Plan Review Notes For Permit 14020956 |
| Permit Number |
14020956 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-25 18:48:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | 1. SEE PAGE 9 OF 19, GEOTECHNICAL REPORT PREPARED BY | | | GFA: | | | | | | "THE GROUND IMPROVEMENT PLAN SHOULD BE REVIEWED IN | | | CONCERT BY THE GEOTECHNICAL ENGINEER AND STRUCTURAL | | | ENGINEER FOR CONFORMANCE WITH THE INTENT OF THE | | | FOUNDATION DESIGN. IN ADDITION, THE INSTALLATION OF THE | | | PIERS SHOULD BE MONITORED CONTINUOUSLY BY GFA TO VERIFY | | | DEPTH OF PIER AND THAT THE PIER IS CONTINUOUS TO THE | | | GROUND SURFACE." | | | | | | THE PLAN HAS BEEN REVIEWED BY THE EOR, BUT NOT BY THE | | | GEOTECHNICAL ENGINEER. PLEASE HAVE REVIEWED AND ALSO | | | INDICATE INTENT TO HAVE INSTALLATION MONITORED BY GFA. | | | THIS MAY BE DONE VIA LETTER. | | | | | | |
|