| Plan Review Notes For Permit 14020917 |
| Permit Number |
14020917 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-05 09:40:39 | THE PERMIT PLAN WAS REVIEWED WITH THE FOLLOWING | | | COMMENTS SUBMITTED BY PETER LEDUC, FIRE MARSHAL, BUREAU | | | OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE. | | | | | | THE PERMIT PLAN IS APPROVED WITH THE FOLLOWING | | | COMMENTS. | | | | | | 1. A SEPARATE FIRE SPRINKLER SYSTEM SHOP DRAWINGS, | | | COMPLAINT WITH NFPA 13, IS REQUIRED TO BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | | PRIOR TO ANY INSTALLATION. | | | | | | 2. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE | | | DONE BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP | | | DRAWINGS COMPLIANT WITH NFPA 72 IS REQUIRED TO BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION | | | BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 3. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND FIRE ALARM, EXCEEDS 4 HOURS, A FIRE WATCH | | | SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL AND | | | COMPLETE PROTECTION IS RETURNED. | | | | | | 4. ENSURE THAT EMERGENCY EXIT LIGHTING IS SUPPLIED FOR | | | THE EXITS AND EXITS PATHS. A COMBINATION EXIT/EMERGENCY | | | IS ACCEPTABLE. | | | | | | |
|