Plan Review Notes
Plan Review Notes For Permit 14020902
Permit Number 14020902
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-03 11:49:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 2. ON THE PRODUCT APPROVAL, GLASS OPTIONS ARE CIRCLED
 BUT INDICATE 38" AND 50" HIGH WINDOWS. PLAN SHOWS 50"
 AND 73" HIGH WINDOWS. PLEASE REVISE. IF 38" HIGH
 WINDOWS ARE PROPOSED, REVISE FLOOR PLAN AND INCLUDE
 ROOM DESIGNATION FBC R310, FBC EB 604.1.
  
  
  