Text |
| 2014-03-14 16:27:51 | PLUMBING PLAN REVIEW |
| | PERMIT:14020875 |
| | ADD: 901 45TH ST |
| | CONT: WESTBROOKE |
| | TEL: (561)395-4126 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY MARCH 14/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE CONFIRMATION IN ROOMS 105 & 112 THERE |
| | ALREADY EXIST FLOOR SINKS, THEY DO NOT APPEAR ON THE |
| | DEMO PLAN, SHEET A111 THE FLOOR SINK IS INDICATED IN |
| | ROOM 101, IN ROOM 112 THERE REMAINS A CABINET AND SINK. |
| | NEITHER THE DEMO OR ARCHITECTURAL INDICATE AN EXISTING |
| | FLOOR SINK PLEASE VERIFY EXISTING OR IS THIS NEW WORK. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET P211 INDICATES THIS TO BE A GRAVITY WASTE |
| | PIPING SYSTEM, ACTUALLY 2 INDEPENDANT SYSTEMS. THE |
| | PLANS ARE NOT CLEAR IF THE GRAVITY LINES |
| | (PIPES) ARE LOCATED ABOVE THE FLOOR SLAB OR BELOW AND |
| | IF THE CENRALLY LOCATED SUMP PUMP TANK EXTENDS BENEATH |
| | THE FLOOR SLAB. A THERE ARE 2 CONCERNS OF INTEREST THAT |
| | WILL NEED TO BE STATISFIED OR CLARIFIED. |
| | 2A) THE PLANS INDICATE ON THE SUMP PUMP CONTAINER THE |
| | USE OF A AIR ADMITANCE VALVE. 2010 FBC-P WOULD REQUIRE |
| | THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM (FLUID |
| | SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR |
| | ABOVE THE ROOF. IS THERE A VACUUM PUMP INSTALLED WITHIN |
| | THIS SYSTEM? IS THIS TRUELY 2 INDEPENDANT DISPOSAL |
| | SYSTEMS. |
| | |
| | 2B) THE SECOND ISSUE IS THE SUMP DRAIN DETAIL FOUND ON |
| | P211 SHOWS A 2 INCH INDIRECT WASTE AND FUNNEL DRAIN. |
| | 2010 FBC-P 713.7 CENTRAL VACUUM OR DISPOSAL SYSTEMS. |
| | WHERE THE WASTE FROM A CENTRAL VACUUM (FLUID SUCTION) |
| | SYSTEM OF THE BAROMETRIC-LAG, COLLECTION-TANK OR |
| | BOTTLE-DISPOSAL TYPE IS CONNECTED TO THE DRAINAGE |
| | SYSTEM, THE WASTE SHALL BE DIRECTLY CONNECTED TO THE |
| | SANITARY DRAINAGE SYSTEM THROUGH A TRAPPED WASTE. THIS |
| | IS INTENDED TO MINIMIZE POSSIBLE CONTAMINATION BY |
| | PREVENTING THE WASTE FROM BEING EXPOSED TO THE |
| | ATMOSPHERE. |
| | |
| | 3) SHEET A111 ROOM 122 SHOW RO (REVERSE OSMOSIS) |
| | MACHINE, WATER SOFTNER, EXCHANGE CARBONS AND BUSTER |
| | PUMPS BUT THE PLUMBING PLANS DO NOT PROVIDE HOW THESE |
| | SYSTEMS OPERATE, THERE ARE NO MANUFACTURER CUT SHEET ON |
| | THIS EQUIPMENT, THERE IS NOT ENOUGH INFORMATION |
| | PROVIDED, A THOROUGH REVIEW CAN NOT BE MADE AT THIS |
| | TIME, AS A RESULT OF THE ADDITIONAL INFORMATION |
| | REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT |
| | PART OF THIS REVIEW. |
| | |
| | |
| | |