| 2014-03-25 11:20:09 | 14020875 | | | 901 45TH STREET | | | ST. MARY?S INC. - TEMP DIALYSIS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | SHEET E001 | | | THE FEEDER FROM THE TEMPORARY GENERATOR TO THE ATS | | | DOES NOT APPEAR TO BE PROPERLY SIZED. MAXIMUM | | | OVERCURRENT PROTECTION FOR 3/0 CU. IS LIMITED TO 200 | | | AMPS. NEC 310.16 | | | | | | SHEET E211 | | | INDICATE ON THE PLAN THE APPROPRIATE WIRING METHOD | | | NECESSARY TO PROVIDE AN EFFECTIVE GROUND FAULT CURRENT | | | PATH FOR THE BRANCH CIRCUITS AND PANEL BOARDS SERVING | | | THE PATIENT CARE AREAS. NEC 517.13; 517.14 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE | | | GENERATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|