2014-03-25 11:20:0914020875
 901 45TH STREET
 ST. MARY?S INC. - TEMP DIALYSIS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHEET E001
  THE FEEDER FROM THE TEMPORARY GENERATOR TO THE ATS
 DOES NOT APPEAR TO BE PROPERLY SIZED. MAXIMUM
 OVERCURRENT PROTECTION FOR 3/0 CU. IS LIMITED TO 200
 AMPS. NEC 310.16
  
 SHEET E211
  INDICATE ON THE PLAN THE APPROPRIATE WIRING METHOD
 NECESSARY TO PROVIDE AN EFFECTIVE GROUND FAULT CURRENT
 PATH FOR THE BRANCH CIRCUITS AND PANEL BOARDS SERVING
 THE PATIENT CARE AREAS. NEC 517.13; 517.14
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 GENERATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW