| Plan Review Notes For Permit 14020863 |
| Permit Number |
14020863 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-21 12:03:06 | THE MISSING PAGES WERE PRESENTED FOR REVIEW AND | | | FOLLOWING ARE THE ITEMS NEEDING FURTHER ATTENTION: | | | 1. AS PER FBC- 1006.2.1(2), EMERGENCY LIGHTING IS | | | REQUIRED IN THE BATHROOMS, WORK ROOMS AND ANY OTHER | | | ROOM NOT HAVING WINDOWS. | | | 2. WILL THE EXISTING ELECTRICAL PANELS & TRANSFORMER BE | | | RELOCATED TO THE LOCATION INDICATED ON THE PLANS, OR | | | WILL THEY BE RELOCATED FROM THERE TO A A NEW LOCATION. | | | PLEASE CLARIFY. | | | 3. PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING | | | CONDUCTOR SIZING AND WIRING METHOD. | | 2014-03-05 18:15:55 | THE ELECTRICAL REVIEW FAILED DUE TO AN INCOMPLETE SET | | | OF ELECTRICAL PLAN SUBMISSION. PROVIDE THE REMAINDER OF | | | THE ELECTRICAL SHEETS FOR THE NEXT REVIEW. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | | | | RETURNED FILE TO BIN FOR FURTHER REVIEWS |
|