| Plan Review Notes For Permit 14020825 |
| Permit Number |
14020825 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-26 18:23:54 | ELECTRICAL PROVISO: | | | AS PER NEC 682.11 THIS SERVICE SHALL DISCONNECT (SHUNT | | | TRIP) WHEN THE WATER LEVEL REACHES THE HEIGHT OF THE | | | ESTABLISHED ELECTRICAL DATUM PLANE. | | | REVIEWED BY MIKE ALBARRAN :(561) 805-6718 |
|