| 2014-02-24 17:41:08 | THE FOLLOWING ITEMS ARE MISSING FROM THE SUBMITTED | | | DRAWING FOR APPROVAL: | | | 1. INDICATE THE PROPOSED LOCATION OF THE SERVICE IN | | | RELATION AND COMPLIANCE WITH THE NEC 682 DATUM | | | ELECTRICAL PLANE. | | | 2. NEC 682.11 REQUIRES A SHUNT TRIP OR SIMILAR DEVICE | | | TO SHUT DOWN THIS SERVICE SHOULD THE WATER RISE ABOVE | | | THE ELECTRICAL DATUM PLANE. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBERTAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|