| Plan Review Notes For Permit 14020792 |
| Permit Number |
14020792 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-26 15:05:22 | REVIEW #: 1 | | | ACTION: DENIED | | | | | | FBC 2010 CODE FAMILY W/ 2012 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING DEFICIENCIES HAVE BEEN FOUND ON THE | | | SUBMITTED PLANS. | | | | | | 1. PAGE M-2.1 SHOWS A BIFOLD DOOR ON THE NEW A/C | | | CLOSET. THE BIFOLD DOOR IS MADE OF WOOD PER THE DOOR | | | SCHEDULE ON PAGE A-1.2. THIS CLOSET CONSTITUTES A | | | PLENUM. THEREFORE, A WOOD DOOR, OR ANY OTHER | | | COMBUSTIBLE MATERIAL, IS NOT PERMITTED. SHOW ALL | | | MATERIALS EXPOSED TO THE PLENUM ARE NON-COMBUSTIBLE PER | | | FBC-M 606.2.1. | | | | | | 2. PAGE M-2.1 SHOWS THE VENTILATION AIR INTAKE OPENING | | | ON A SIDE OF THE BUILDING WHICH FRONTS A STREET OR | | | DRIVEWAY. INTAKE OPENINGS SHALL BE MIN. 10 FEET FROM | | | SUCH LOCATIONS PER FBC-M 401.4.1. | | | | | | 3. NO SYSTEM SIZING CALCULATIONS PROVIDED. SIZING OF | | | SYSTEMS SHALL BE DETERMINED IN ACCORDANCE WITH FBC-EC | | | 503.2. PROVIDE CALCULATIONS. | | | | | | PLEASE MAKE NECESSARY CORRECTIONS ON PLANS AND RESPOND | | | TO EACH COMMENT IN WRITING, EXPLAINING HOW THE COMMENT | | | WAS ADDRESSED AND WHERE THE PROVIDED INFORMATION CAN BE | | | LOCATED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|