| Plan Review Notes For Permit 14020586 |
| Permit Number |
14020586 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-16 11:39:17 | MINIMUM PLAN REVIEW CRITERIA. FBC- 107.3.5.3 ? | | | | | | PROVIDE LOAD CALCULATIONS BASED ON THE NEW ACTUAL | | | CONNECTED LOAD. CALCULATIONS INDICATE 2 SMALL APPLIANCE | | | KITCHEN CIRCUITS. THIS SHOULD BE REMOVED AS A KITCHEN | | | MAY NOT BE PERMITTED WITHIN THE STRUCTURE. THE LOAD | | | CALCULATIONS SHOULD INDUCATE THE EXISTING SERVICE IS | | | ADEQUATE TO ACCOMODATE THE NEW, ALTHOUGH SMALL, | | | PROPOSED LOAD. NOTE INDICATES GFI FOR BATH AREA, NO GFI | | | TO SERVICE BATH IS PROVIDED. | | | |
|