 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4' TO THE BACKSIDE. THE DETAIL ON SHEET C19
 REFLECTS THESE CLEARANCES; HOWEVER, THE MAJORITY OF THE
 HYDRANTS ON THE PLAN SHEETS ARE LOCATED IN THE 10'-0"
 WIDE PARKING ISLANDS WHICH WILL NOT ALLOW PROPER
 CLEARANCES DUE TO ALLOTED PARKING SPACES ON EACH SIDE
 OF THE HYDRANT. PROPOSE ELIMINATING THE PARKING SPACES
 ON EACH SIDE OF THE HYDRANT. SPACES SHALL BE MARKED AS
 NO PARKING WITH SIGNAGE AND PAVEMENT PAINT. PER SECTION
 18.2.3.5.3 (NFPA 1), FIRE EQUIPMENT AND LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12"X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTIONS.
  
 PROVIDE A DRAWING NOTE INDICATING FIRE HYDRANTS ARE
 REQUIRED TO BE INSPECTED, TESTED AND APPROVED BY THE
 FIRE DEPARTMENT PRIOR TO ANY VERTICAL CONSTRUCTION OR
 THE STORAGE OF COMBUSTIBLES.
  