| 2014-08-06 16:08:37 | BUILDING PROVISO: |
| | |
| | SHEET AE101B & AE101F THE MAIN ENTRY GATE BETWEEN THE |
| | FITNESS CENTER & BISTRO WILL NEED TO MEET BOTH |
| | REQUIREMENTS FOR EGRESS: |
| | |
| | 2010 FBC-B 424.1.3.1.9. ACCESS THROUGH THE BARRIER OR |
| | FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, |
| | MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH |
| | SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH |
| | (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH |
| | THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM |
| | THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) |
| | BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE |
| | SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING |
| | AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR |
| | INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF |
| | SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864 |
| | MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED |
| | FLOOR OR GROUND. GATES SHALL OPEN OUTWARD AWAY FROM THE |
| | POOL AREA. |
| | |
| | 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | THE GATES WILL NEED TO BE DESIGNED SO PANIC HARDWARE |
| | (1008.1.10) WILL BE INSTALLED ON THE INTERIOR SIDE OF |
| | THE GATE AND THE EXTERIOR SIDE WILL HAVE A RELEASING |
| | MECHANISM LOCATED AT 54 INCHES ABOVE THE |
| | DECK(424.1.1.9) . THE RELEASING MECHANISM WILL NEED TO |
| | BE TIED INTO THE PANIC HARDWARE RELEASING MECHANISM. |
| | NOTE THE CONCERNS OF A CHILD ON THE EXTERIOR SIDE OF |
| | THE GATE WILL NOT BE ABLE TO ACTIVATE THE PANIC |
| | HARDWARE AND GAIN ENTRY INTO THE POOL AREA. THE GATE |
| | WILL HAVE TO HAVE SELF CLOSING AND SELF LATCHING |
| | HARDWARE. |
| | |
| | THIS TYPE OF SITUATION WILL NEED TO BE ADDRESSED ON ALL |
| | GATES AND OR DOORS THAT LEAD TO THE POOL DECK FROM THE |
| | EXTERIOR. |
| | |