| Plan Review Notes For Permit 14020547 |
| Permit Number |
14020547 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2014-07-01 15:26:06 | ****PROVISOS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER, [email protected], | | | 561-805-6724 | | | 1. PER APPLICANT, SCOPE OF THIS FOUNDATION PERMIT IS | | | LIMITED TO VIBROCOMPACTION, BELOW GRADE FOUNDATIONS, | | | AND WATER, SEWER AND STORM PIPING. | | | 2. PER APPLICANT, PLAT PLAN HAS BEEN SUBMITTED. | | | 3. FBC 110.7 IMPACT OF CONSTRUCTION. PER MANNY | | | GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN FILED | | | WITH THE ENGINEERING DEPARTMENT. | | | 4. INFORMATIONAL SHEETS NOT RELATED TO FOUNDATION HAVE | | | NOT BEEN REVIEWED. | | | 5. REVISE SHEET S5.1, TYPICAL CONCRETE COLUMN, TO | | | REMOVE TEXT RELATED TO PILE CAPS. | | | 6. PRIOR TO RESUBMITTAL OF THE BUILDING PLANS, PERMIT | | | 14030096, PLEASE CONTACT CAROLINE PUELL, 561.805.6659, | | | [email protected] TO DISCUSS NAMING CONVENTION FOR THE | | | FILES. FOUNDATION PLAN SHEETS WERE NOT NAMED IN A | | | MANNER WHICH IS EXPEDITIOUS FOR PLAN REVIEW. MS. PUELL | | | IS ABLE TO GIVE GUIDANCE IN THIS AREA. | | | |
|