| 2014-05-01 18:09:40 | PLUMBING PLAN REVIEW |
| | LOFTIN PLACE -FOUNDATION PERMIT |
| | PERMIT: 14020547 |
| | ADD: 705 N OLIVE AVE |
| | CONT: KAST CONSTRUCTION |
| | TEL: (561)689-2910 |
| | CONTACT: NEYITA (561)856-6655 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: THURSDAY MAY 01/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING |
| | SANITARY DRAINAGE |
| | VENTS |
| | ROOF DRAINAGE |
| | SAND INTERCEPTOR OR TRAPS |
| | ENVIRONMENTAL REQUIREMENTS |
| | PLUMBING RISER |
| | |
| | 2A) 2ND REQUEST, SHEET P-2.1.1.A INDICATES A 8 INCH |
| | PIPE FOR GARAGE DRAINAGE TO SAND FILTER SEE CIVIL DWGS, |
| | IF THE PLANS SHOW A SAND FILTER TO GET RID OF OILY |
| | WATER PLEASE PROVIDE DETAILS FOR SUCH FILTER. AS IN |
| | YOUR RESPONCE PARKING GARGES DO NOT REQUIRE THE SAND |
| | FILTER BUT YOU AS THE DESIGNER REQUIRE IT, SHOWN ON |
| | TTHE PLANS THEN WE WILL NEED THE BACK UP LITERATURE FOR |
| | THE SIZING OF THE SAND FILTER. |
| | |
| | PLEASE COMPLY WITH 2010 FBC-P 1003.1 WHERE REQUIRED. |
| | INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO |
| | PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER |
| | SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING |
| | DRAINAGE SYSTEM, THE PUBLIC SEWER, THE PRIVATE SEWAGE |
| | DISPOSAL SYSTEM OR THE SEWAGE TREATMENT PLANT OR |
| | PROCESSES. |
| | |
| | 2B) 2ND REQUEST. 1003.11 (IPC 1003.5) SAND INTERCEPTORS |
| | IN COMMERCIAL ESTABLISHMENTS. SAND AND SIMILAR |
| | INTERCEPTORS FOR HEAVY SOLIDS SHALL BE DESIGNED AND |
| | LOCATED SO AS TO BE PROVIDED WITH READY ACCESS FOR |
| | CLEANING,AND SHALL HAVE A WATER SEAL OF NOT LESS THAN 6 |
| | INCHES (152 MM). |
| | |
| | 2C) COMPLIED. |
| | |
| | 2D) 2ND REQUEST, THIS MAY BE A FOUNDATION PERMIT BUT |
| | THE ROOF DRAINAGE IS SIZED FROM THE ROOF AREA AND 1/2 |
| | OF THE HEIGHT OF THE PARAET WALLS, THE PLANS ALSO FAIL |
| | TO PROVIDE THE CRITERIA FOR SIZING OF THE ROOF |
| | DRAINAGE, 2010 FBC-P 1106.1 WITH OUT THIS INFORMATION |
| | WE CAN NOT BE SURE THE CONDUCTORS ARE SIZED PROPERLY. |
| | 100 YEAR 1 HOUR RAIN FALL 4,5 INCHES. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5.1.3 |
| | PLUMBING ROOF DRAINAGE ISOMETRIC FOR THE BUILDING. |
| | PLEASE NOTE THE SHEET INDICATED IN THE DRAWING FILE AS |
| | 471-P-2.19 IS ACTUALLY SHEET P-218. THE ROOF DECK |
| | DRAINAGE SHEET. |
| | |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) 2ND REQUEST. THE RESPONSE INDICATES SHEET P6.1 NOTE |
| | FOR TRAP RESEAL, NOT A TRAP PRIMER. PLEASE REVIEW 2010 |
| | FBC-P |
| | THE PLANS INDICATE THE USE OF FLOOR DRAINS IN THE |
| | GARAGE, FIRE PUMP ROOM, DOMESTIC PUMP ROOM AND TREASH |
| | ROOMS WITH OUT THE USE OF TRAP PRIMER VALVES. |
| | 2010 FBC-P 1002.3 PROHIBITED TRAPS. |
| | THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS |
| | THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL. |
| | |
| | 1002.4 TRAP SEALS. |
| | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| | ASSE 1044. |
| | |
| | 6) PLEASE NOTE SHOWER ARE BASED ONTHE TOTAL FLOW RATE |
| | THROUGH SHOWER HEADS AND BODY SPRAYS A 2 INCH TRAP WILL |
| | ALLOW FOR 5.7 GPM TO 12.3 GPM PER FBC-P TABLE 709.1. NO |
| | ACTION IS REQUIRED, JUST INFORMATIONAL. |
| | |
| | 7) PROJECT DOCS < A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |