| 2014-02-25 14:40:59 | 705 NORTH OLIVE AVENUE |
| | PERMIT #14020547 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****FOUNDATION PERMIT ONLY - CONTRACTOR PROCEEDING AT |
| | RISK***** |
| | |
| | PER NFPA 20, THE LOCATION OF THE FIRE PUMP SHALL BE |
| | PRE-APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | PER NFPA 241, FIRE HYDRANTS SHALL BE INSTALLED, TESTED |
| | AND INSPECTED PRIOR TO ANY VERTICAL CONSTRUCTION. |
| | |
| | PER NFPA 1 SECTION 18.4 INDICATE THE BUILDING/SITE FIRE |
| | FLOW REQUIREMENTS. |
| | |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 |
| | TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM |
| | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| | TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | PER NFPA 1 SECTION 18.3.4.1, FIRE HYDRANTS SHALL BE |
| | PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND |
| | SIDES AND 4' TO THE BACKSIDE. |
| | |
| | PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE |
| | FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE |
| | ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO |
| | THAT THEY CAN BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |