| Plan Review Notes For Permit 14020542 |
| Permit Number |
14020542 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-25 10:04:51 | 14020542 | | | 550 OKEECHOBEE BLVD | | | SURVEILLANCE CAMERA INSTALLATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A COMMUNICATIONS RISER PLAN SHOWING ALL DEVICES | | | AND WIRING METHODS. INCLUDE SPECIFICATIONS SHOW THE | | | LISTING OF ALL EQUIPMENT AND WIRING METHODS. NEC 110.8, | | | 800.48, 800.113 | | | PROVIDE A FIRE AND SMOKE STOPPING DETAIL FOR ALL WALL | | | AND FLOOR PENETRATIONS. NEC 800.26, 800.154 | | | NOTE THAT ALL WIRING METHODS LOCATED BELOW GRADE MUST | | | BE RATED FOR THE LOCATION. NEC 110.11 | | | NOTE THAT ALL ABANDONED CABLE MUST BE REMOVED. NEC | | | 800.25 | | | PROVIDE SPECIFICATIONS ON THE NEW CAMERAS. NEC | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | | | | |
|