2014-02-25 10:04:5114020542
 550 OKEECHOBEE BLVD
 SURVEILLANCE CAMERA INSTALLATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A COMMUNICATIONS RISER PLAN SHOWING ALL DEVICES
 AND WIRING METHODS. INCLUDE SPECIFICATIONS SHOW THE
 LISTING OF ALL EQUIPMENT AND WIRING METHODS. NEC 110.8,
 800.48, 800.113
 PROVIDE A FIRE AND SMOKE STOPPING DETAIL FOR ALL WALL
 AND FLOOR PENETRATIONS. NEC 800.26, 800.154
 NOTE THAT ALL WIRING METHODS LOCATED BELOW GRADE MUST
 BE RATED FOR THE LOCATION. NEC 110.11
 NOTE THAT ALL ABANDONED CABLE MUST BE REMOVED. NEC
 800.25
 PROVIDE SPECIFICATIONS ON THE NEW CAMERAS. NEC
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  
  