Plan Review Notes
Plan Review Notes For Permit 14020538
Permit Number 14020538
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-04 14:58:43PLANS HAVE INCONSISTANCIES. SHEET E-2 SHOWS A 480V
 UTILITY SERVICE WITH A 240V PANEL. PANEL SCHEDULE LOAD
 CALCS ARE INCONSISTANT WITH INFORMATION GIVEN IN THE
 PANEL SCHEDULES. GROUNDING DETAILS SHOWN ON SHEET E-5
 BUT NOT SPECIFIED ON SHEET E-2. DAH