| Plan Review Notes For Permit 14020538 |
| Permit Number |
14020538 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-04 14:58:43 | PLANS HAVE INCONSISTANCIES. SHEET E-2 SHOWS A 480V | | | UTILITY SERVICE WITH A 240V PANEL. PANEL SCHEDULE LOAD | | | CALCS ARE INCONSISTANT WITH INFORMATION GIVEN IN THE | | | PANEL SCHEDULES. GROUNDING DETAILS SHOWN ON SHEET E-5 | | | BUT NOT SPECIFIED ON SHEET E-2. DAH |
|