| Plan Review Notes For Permit 14020501 |
| Permit Number |
14020501 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-02-27 17:16:28 | RESIDENTIAL (R3) SOLAR ATTIC FAN INSTALLATION, SECOND | | | BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PRODUCT EVALUATION REPORT #1938 FROM FLORIDA PRODUCT | | | APPROVAL FL13509-R1 STATES THAT THIS PRODUCT APPROVAL | | | IS ONLY FOR ASPHALT SHINGLES INSTALLATION. THE PROPOSED | | | INSTALLATION IS ON A CONCRETE TILE ROOF AND ON A FLAT | | | ROOF. NEED PRODUCT APPROVAL FOR THE PROPOSED | | | INSTALLATION AS REQUIRED BY DCA RULE 9N-3. | | | | | | ***INFORMATION SUBMITTED FOR FLORIDA PRODUCT APPROVAL | | | FL13509-R1 DOESN'T MATCH THE INFORMATION THAT WAS | | | SUBMITTED TO THE FLORIDA BUILDING COMMISSION FOR | | | APPROVAL. NEED TO PROVIDE THE PRODUCT EVALUATION REPORT | | | "PTC REPORT #1938". THIS IS THE PRODUCT EVALUATION | | | REPORT THAT WAS APPROVED AND STATES THAT PRODUCT | | | APPROVAL IS FOR SHINGLES INSTALLATION ONLY. | | | "EQUIVALENCY OF STANDARDS EVALUATION TO 2010 FBC" | | | REPORT #1939 SUBMITTED NOW IS NOT PART OF THE APPROVED | | | PACKAGE. | | | | | | | | | *** AS AN ALTERNATIVE, MANUFACTURER MAY APPLY LOCAL | | | PRODUCT APPROVAL BY PROVIDING COMPLETE ENGINEERING | | | PACKAGE FOR REVIEW AND APPROVAL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|