2014-02-27 17:16:28RESIDENTIAL (R3) SOLAR ATTIC FAN INSTALLATION, SECOND
 BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PRODUCT EVALUATION REPORT #1938 FROM FLORIDA PRODUCT
 APPROVAL FL13509-R1 STATES THAT THIS PRODUCT APPROVAL
 IS ONLY FOR ASPHALT SHINGLES INSTALLATION. THE PROPOSED
 INSTALLATION IS ON A CONCRETE TILE ROOF AND ON A FLAT
 ROOF. NEED PRODUCT APPROVAL FOR THE PROPOSED
 INSTALLATION AS REQUIRED BY DCA RULE 9N-3.
  
 ***INFORMATION SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 FL13509-R1 DOESN'T MATCH THE INFORMATION THAT WAS
 SUBMITTED TO THE FLORIDA BUILDING COMMISSION FOR
 APPROVAL. NEED TO PROVIDE THE PRODUCT EVALUATION REPORT
 "PTC REPORT #1938". THIS IS THE PRODUCT EVALUATION
 REPORT THAT WAS APPROVED AND STATES THAT PRODUCT
 APPROVAL IS FOR SHINGLES INSTALLATION ONLY.
 "EQUIVALENCY OF STANDARDS EVALUATION TO 2010 FBC"
 REPORT #1939 SUBMITTED NOW IS NOT PART OF THE APPROVED
 PACKAGE.
  
  
 *** AS AN ALTERNATIVE, MANUFACTURER MAY APPLY LOCAL
 PRODUCT APPROVAL BY PROVIDING COMPLETE ENGINEERING
 PACKAGE FOR REVIEW AND APPROVAL.
  
  