| 2014-05-01 18:04:46 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SHOW COMPLIANCE WITH FBC R318.6 WHICH REQUIRES |
| | GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF |
| | LESS THAN 6 INCH HORIZONTAL PROJECTION. GUTTERS ARE |
| | REQUIRED ANYWHERE THE ROOF IS SLOPED TO DRAIN THE WATER |
| | FROM THE ROOF AND THE EAVES OVERHANG LESS THAN 6 |
| | INCHES. |
| | |
| | 2) SHEET S-1 HAS BASE SHEET ENHANCED FASTENING |
| | CALCULATIONS FOR GAF MODIFIED ROOFING NOA NUMBER |
| | 12-1003.05. PLEASE SUBMIT TWO COPIES OF THE PRODUCT |
| | APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD. DCA RULE 9N-3 |
| | |
| | 3) THE BASE SHEET ENHANCED FASTENING CALCULATIONS ON |
| | SHEET S-1 STATE THEY ARE FOR A ROOF HEIGHT OF LESS THAN |
| | 15'. THE PLANS SHOW THAT THE ROOF HEIGHT IS MORE THAN |
| | 20'. PLEASE REVISE TO SHOW ROOF HEIGHT OF LESS THAN |
| | 25'. FBC R301.2.1 |
| | |
| | 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | CONNECTORS, HANGERS AND ANCHORS SHOWN ON THE PLANS OR |
| | SPECIFY THE PRODUCT APPROVAL NUMBER FOR EACH ON THE |
| | PLANS. DCA RULE 9N-3 THE ONE THAT WAS SUBMITTED DID NOT |
| | INCLUDE THE SIMPSON LUS210, HM9KT, ABU66 AND BCS2-3/6 |
| | CONNECTORS. |
| | |
| | 5) THE PLANS SHOW BARREL TILE ON THE COVERED PATIO |
| | ROOF. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | ROOF TILE THAT WILL BE USED. SPECIFY HOW IT WILL BE |
| | ATTACHED TO RESIST OVERTURNING MOMENT BY MARKING ONE OF |
| | THE FASTENING OPTIONS ON THE PRODUCT APPROVAL. IF |
| | ADHESIVES ARE TO BE USED FOR TILE INSTALLATION, SUBMIT |
| | TWO C0PIES OF ITS PRODUCT APPROVALS AS REQUIRED BY DCA |
| | RULE 9N-3. |
| | |
| | 6) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 7) THE PRODUCT APPROVAL INSTALLATION DRAWINGS FOR THE |
| | FRENCH DOORS AND LAWSON SINGLE HUNG WINDOWS WERE NOT |
| | SHRUNK TO FIT ON 8.5" X 11" PAPER WHEN THEY WERE |
| | PRINTED. THIS CAUSED SOME OF THE REQUIRED INFORMATION |
| | TO BE MISSING FROM THE DRAWINGS. SUBMIT COMPLETE |
| | INSTALLATION DRAWINGS. DCA RULE 9N-3 |
| | |
| | 8) IN ORDER TO SPEED THE PLAN REVIEW PROCESS, PLEASE |
| | SUBMIT A RESPONSE LETTER WITH THE RE-SUBMITTAL |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS WAS |
| | ADDRESSED. |
| | |