Plan Review Notes
Plan Review Notes For Permit 14020487
Permit Number 14020487
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-02-25 16:12:55THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THE PERMIT IS APPROVED WITH THE FOLLOWING COMMENTS.
  
 1. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS
 REQUIRED FOR THIS BUILD-OUT. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
 ANY TIME THE SYSTEM IS DOWN FOR MORE THAN 4 HOURS A
 FIRE WATCH IS REQUIRED.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE BY A CERTIFIED FIRE ALARM CONTRACTOR. A SEPARATE
 SHOP DRAWINGS COMPLIANT WITH NFPA 72 IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 3. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.