2014-05-21 07:50:19PREAPRED TO ISSUE WITH ELECTRICAL PROVISO:
  
 1) PROVIDE SMOKE DETECTORS AS REQUIRED FOR NEW
 DWELLINGS. FBC-R314.3.1, 315.1, FBC 107.3.5 PLEASE
 PROVIDE ONE ADDITIONAL SMOKE/CO DETECTOR AT THE FIRST
 AND SECOND FL LANDINGS.
  
 2) RECESSED LIGHTS. REQUIRES THAT RECESSED LUMINAIRES
 BE SEALED, AIR TIGHT, IC RATED. 2010 FBC 402.4.5
  
 3) PROTECTION FROM PHYSICAL DAMAGE TO BE PROVIDED FOR
 ELECTRICAL PANELS IN GARAGE. NEC 110.27 B
  
 4) PROVIDE THE ARC FAULT CALCULATION TO INDICATE THE
 AIC RATING ON SERVICE SWITCHGEAR. NEC 110.9 AND 110.10
  
 5) PROVIDE CUT SHEETS ON INFLOOR UP LIGHTS AND DROP
 DOWN SCREENS TO INDICATE COMPLIANCE WITH THE NEC 110.3
  
 6) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. THOSE
 OUTLETS IN WET LOCATIONS SHALL BE GFI & WEATHER
 RESISTANT NEC 406.8(B), 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.