| Plan Review Notes For Permit 14020415 |
| Permit Number |
14020415 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-05-21 07:50:19 | PREAPRED TO ISSUE WITH ELECTRICAL PROVISO: | | | | | | 1) PROVIDE SMOKE DETECTORS AS REQUIRED FOR NEW | | | DWELLINGS. FBC-R314.3.1, 315.1, FBC 107.3.5 PLEASE | | | PROVIDE ONE ADDITIONAL SMOKE/CO DETECTOR AT THE FIRST | | | AND SECOND FL LANDINGS. | | | | | | 2) RECESSED LIGHTS. REQUIRES THAT RECESSED LUMINAIRES | | | BE SEALED, AIR TIGHT, IC RATED. 2010 FBC 402.4.5 | | | | | | 3) PROTECTION FROM PHYSICAL DAMAGE TO BE PROVIDED FOR | | | ELECTRICAL PANELS IN GARAGE. NEC 110.27 B | | | | | | 4) PROVIDE THE ARC FAULT CALCULATION TO INDICATE THE | | | AIC RATING ON SERVICE SWITCHGEAR. NEC 110.9 AND 110.10 | | | | | | 5) PROVIDE CUT SHEETS ON INFLOOR UP LIGHTS AND DROP | | | DOWN SCREENS TO INDICATE COMPLIANCE WITH THE NEC 110.3 | | | | | | 6) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. THOSE | | | OUTLETS IN WET LOCATIONS SHALL BE GFI & WEATHER | | | RESISTANT NEC 406.8(B), 406.11 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] |
|