| 2014-04-29 14:44:13 | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 |
| | SPECIFICATIONS AND CUT SHEETS FOR THE ELEVATOR, |
| | GENERATOR AND THE ATS IN ORDER TO DO A COMPLETE |
| | ELECTRICAL REVIEW 110.3 |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | A SIGN IS REQUIRED AT THE SERVICE ENTRANCE TO INDICATE |
| | THE TYPE AND LOCATION OF THE OPTIONAL STANDBY SYSTEM. |
| | 702 |
| | EQUIPMENT GROUNDING CONDUCTORS IN PARALLEL TO BE FULL |
| | SIZED 250.122 (F) PLANS DO NOT INDICATE AN EQUIPMENT |
| | GROUND FROM THE GENERATOR AS REQUIRED 250.122. PLEASE |
| | ADJUST THE RISER TO INDICATE A FULL SIZE EQUIPMENT |
| | GROUNDING CONDUCTOR RUN WITH THE GENERATOR FEEDERS. |
| | EQUIPMENT GROUNDING CONDUCTOR NOT REQUIRED AT SERVICE |
| | ENTRANCE. PLEASE ADJUST THE RISER TO INDICATE ONLY THE |
| | SERVICE ENTRANCE CONDUCTORS WITH THE NEUTRAL (GROUNDED |
| | CONDUCTOR) AT THE 1ST MEANS OF DISCONNECT. AN EQUIPMENT |
| | GOUNDING CONDUCTOR IS REQUIRED AFTER THE 1ST MEANS OF |
| | DISCONNECT BUT NOT BEFORE. 250.6 & 250.24 |
| | EQUIPMENT GOUNDING CONDUCTOR AT THE GENERATOR SHALL BE |
| | BONDED TO THE GOUNDING ELECTRODE. 702.10.B |
| | GAS SERVICE IS REQUIRED TO BE BONDED. 250.104.B. PLEASE |
| | INCLUDE THE GAS SERVICE PIPING IN YOUR GROUNDING |
| | ELECTRODE SYSTEM LINE DAGRAM. |
| | RECESSED LIGHTING TO BE AIRTIGHT. FBC 402.5 PLEASE |
| | INCLUDE A LIGHTING FIXTURE SCHEDULE AND CUT SHEETS FOR |
| | RECESSED LIGHTING. |
| | A MINIMUM OF 50% OF THE LIGHTING INSTALLED SHALL BE |
| | ENERGY EFFICIENT. FBC 404.1 |
| | AT LEAST ONE COUNTERTOP OUTLET IS REQUIRED AT THE |
| | KITCHEN ISLAND. 210.52.C |
| | THE ELEVATOR, GENERATOR, SWIMMING POOL, REQUIRES A |
| | SEPARATE PERMIT. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717, |
| | [email protected]. |