2014-04-29 14:44:13INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
 SPECIFICATIONS AND CUT SHEETS FOR THE ELEVATOR,
 GENERATOR AND THE ATS IN ORDER TO DO A COMPLETE
 ELECTRICAL REVIEW 110.3
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 A SIGN IS REQUIRED AT THE SERVICE ENTRANCE TO INDICATE
 THE TYPE AND LOCATION OF THE OPTIONAL STANDBY SYSTEM.
 702
 EQUIPMENT GROUNDING CONDUCTORS IN PARALLEL TO BE FULL
 SIZED 250.122 (F) PLANS DO NOT INDICATE AN EQUIPMENT
 GROUND FROM THE GENERATOR AS REQUIRED 250.122. PLEASE
 ADJUST THE RISER TO INDICATE A FULL SIZE EQUIPMENT
 GROUNDING CONDUCTOR RUN WITH THE GENERATOR FEEDERS.
 EQUIPMENT GROUNDING CONDUCTOR NOT REQUIRED AT SERVICE
 ENTRANCE. PLEASE ADJUST THE RISER TO INDICATE ONLY THE
 SERVICE ENTRANCE CONDUCTORS WITH THE NEUTRAL (GROUNDED
 CONDUCTOR) AT THE 1ST MEANS OF DISCONNECT. AN EQUIPMENT
 GOUNDING CONDUCTOR IS REQUIRED AFTER THE 1ST MEANS OF
 DISCONNECT BUT NOT BEFORE. 250.6 & 250.24
 EQUIPMENT GOUNDING CONDUCTOR AT THE GENERATOR SHALL BE
 BONDED TO THE GOUNDING ELECTRODE. 702.10.B
 GAS SERVICE IS REQUIRED TO BE BONDED. 250.104.B. PLEASE
 INCLUDE THE GAS SERVICE PIPING IN YOUR GROUNDING
 ELECTRODE SYSTEM LINE DAGRAM.
 RECESSED LIGHTING TO BE AIRTIGHT. FBC 402.5 PLEASE
 INCLUDE A LIGHTING FIXTURE SCHEDULE AND CUT SHEETS FOR
 RECESSED LIGHTING.
 A MINIMUM OF 50% OF THE LIGHTING INSTALLED SHALL BE
 ENERGY EFFICIENT. FBC 404.1
 AT LEAST ONE COUNTERTOP OUTLET IS REQUIRED AT THE
 KITCHEN ISLAND. 210.52.C
 THE ELEVATOR, GENERATOR, SWIMMING POOL, REQUIRES A
 SEPARATE PERMIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717,
 [email protected].