| 2014-03-29 10:23:21 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS. SHOW EQUIPMENT | | | LOCATION AND DUCT SYSTEMS. SPECIFY ALL DUCT SIZES, | | | GRILL SIZES, CFMS AT EACH GRILL. CITY AMENDMENTS | | | 107.3.5 | | | | | | 2) SHOW COMPLIANCE WITH FBC M1602.4 FOR BALANCED RETURN | | | AIR. | | | | | | 3) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS IN COMPLIANCE WITH FBCR M1401.3. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | | CITY AMENDMENTS 107.2.1 | | | | | | 5) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON | | | THE PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|