| Date |
Text |
| 2014-02-08 09:34:56 | 2010 FBC | | | | | | REVISION DENIED | | | | | | 1) THE ROOF WIND DESIGN UPLIFT PRESSURES ARE NOT | | | CORRECT. THE UPLIFTS FOR 170 MPH VULT, EXPOSURE D WITH | | | A 25' MRH ARE -46.2 PSF FOR ROOF ZONE 1, -80.5 PSF FOR | | | ROOF ZONE 2 AND -118.0 PSF FOR ZONE 3. FBC R301.2.1 | | | PLEASE CORRECT. | | | | | | 2) THE VALUE OF THE WORK TO ADD THE COVERED ENTRY TO | | | THE SCOPE OF WORK WAS NOT SPECIFIED ON THE REVISION | | | FORM. CITY AMENDMENTS 109.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|