2014-02-08 09:34:562010 FBC
  
 REVISION DENIED
  
 1) THE ROOF WIND DESIGN UPLIFT PRESSURES ARE NOT
 CORRECT. THE UPLIFTS FOR 170 MPH VULT, EXPOSURE D WITH
 A 25' MRH ARE -46.2 PSF FOR ROOF ZONE 1, -80.5 PSF FOR
 ROOF ZONE 2 AND -118.0 PSF FOR ZONE 3. FBC R301.2.1
 PLEASE CORRECT.
  
 2) THE VALUE OF THE WORK TO ADD THE COVERED ENTRY TO
 THE SCOPE OF WORK WAS NOT SPECIFIED ON THE REVISION
 FORM. CITY AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]