Plan Review Notes
Plan Review Notes For Permit 14020335
Permit Number 14020335
Review Stop Z
Sequence Number 1
Notes
Date Text
2014-03-10 22:18:20FAILED
  
 1) ON SHEET A101:
  
 A. ALIGN THE REAR SIDEWALK WITH THE REAR DOOR FOR BAY
 B14.
 B. DO NOT SHOW CURB LINES UNDER THE TRASH ENCLOSURE
 BEHIND BAY B15.
  
 2) VERIFY THE SCREENING OF THE NEW ROOFTOP UNIT ON
 SHEET A104.
  
 3) PLEASE EXPLAIN WHY ELEVATION SHEET A201 SHOWS A
 DIFFERENT CONDITION THAN THE TENANT BUILD-OUT ELEVATION
 SHEET A-211 TO THE LEFT (SOUTH) OF THE MAIN ENTRANCE
 (PERMIT NO. 14020526)?
  
 4) THIS PERMIT STATES THAT THE TENANT WILL BE
 RESPONSIBLE FOR THE BUILDOUT OF THE FRONT FACADE AROUND
 THE ENTRY DOOR, YET THE BUILDOUT PERMIT REFERS TO A
 METAL PANEL SYSTEM IN THIS AREA "BY OTHERS". PLEASE
 EXPLAIN WHO IS RESPONSIBLE FOR THIS WORK AND UNDER WHAT
 PERMIT IT WILL BE SUBMITTED TO THE CITY.
  
 5) THE AREA OVER BAY B26 ENTRANCE HAS A BLANK WALL AREA
 THAT EXCEEDS 50 FEET IN WIDTH AND 15 FEET IN HEIGHT
 WITH NO ARCHITECTURAL DETAILING OVER THE DOOR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.