| Plan Review Notes For Permit 14020335 |
| Permit Number |
14020335 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-02-25 11:20:20 | YOU WILL NOTICE THAT SEVERAL OF THE REVIEWED PAGES HAVE | | | ALREADY BEEN STAMPED AS APPROVED. THIS IS NOT AN | | | INDICATION THAT THE REVIEW HAS BEEN COMPLETED AND | | | APPROVED. THE FOLLOWING ITEMS SHALL BE ADDRESSED AND | | | CORRECTED ACCORDINGLY SO THE RESPECTIVE PAGES CAN BE | | | STAMPED APPROVED AS WELL. | | | . PAGE E001 | | | 1. AS REQUIRED BY NEC 408.4, THE 45KW LOAD IN PANEL | | | HVB1 SHALL BE IDENTIFIED | | | 2. AS REQUIRED BY NEC 408.4, THE CIRCUIT BREAKERS NOT | | | IN USE SHALL BE LABELED AS SPARES IF THEY ARE TO REMAIN | | | IN THE PANEL. | | | 3. AS PER THE RISER DIAGRAM OF PG. E002, THERE IS A | | | 30KW TRANSFORMER LOAD ON PANEL HVB1 NOT INCLUDED AND | | | IDENTIFIED. | | | 4. AS PER THE NOTES ON THE BOTTOM OF THE PANEL SCHEDULE | | | THERE ARE 2 SETS OF 3/0 NOT INCLUDED OR IDENTIFIED IN | | | THE RISER DIAGRAM. | | | PAGE E203 | | | 1. THE OUTLET REQUIRED BY NEC 600.5 FORMERLY INCLUDED | | | HAS BEEN REMOVED FROM THESE SHEETS. | | | PAGE E204 | | | 1. THE DRAWING IS LABELED ELECTRICAL LIGHTING PLAN, | | | WHEN IT APPEARS TO BE A ROOF PLAN. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|