Plan Review Notes
Plan Review Notes For Permit 14020335
Permit Number 14020335
Review Stop E
Sequence Number 1
Notes
Date Text
2014-02-25 11:20:20YOU WILL NOTICE THAT SEVERAL OF THE REVIEWED PAGES HAVE
 ALREADY BEEN STAMPED AS APPROVED. THIS IS NOT AN
 INDICATION THAT THE REVIEW HAS BEEN COMPLETED AND
 APPROVED. THE FOLLOWING ITEMS SHALL BE ADDRESSED AND
 CORRECTED ACCORDINGLY SO THE RESPECTIVE PAGES CAN BE
 STAMPED APPROVED AS WELL.
 . PAGE E001
 1. AS REQUIRED BY NEC 408.4, THE 45KW LOAD IN PANEL
 HVB1 SHALL BE IDENTIFIED
 2. AS REQUIRED BY NEC 408.4, THE CIRCUIT BREAKERS NOT
 IN USE SHALL BE LABELED AS SPARES IF THEY ARE TO REMAIN
 IN THE PANEL.
 3. AS PER THE RISER DIAGRAM OF PG. E002, THERE IS A
 30KW TRANSFORMER LOAD ON PANEL HVB1 NOT INCLUDED AND
 IDENTIFIED.
 4. AS PER THE NOTES ON THE BOTTOM OF THE PANEL SCHEDULE
 THERE ARE 2 SETS OF 3/0 NOT INCLUDED OR IDENTIFIED IN
 THE RISER DIAGRAM.
 PAGE E203
 1. THE OUTLET REQUIRED BY NEC 600.5 FORMERLY INCLUDED
 HAS BEEN REMOVED FROM THESE SHEETS.
 PAGE E204
 1. THE DRAWING IS LABELED ELECTRICAL LIGHTING PLAN,
 WHEN IT APPEARS TO BE A ROOF PLAN.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE