2014-03-14 18:04:11BUILDING PLAN REVIEW
 REVISION: 14020335
 PERMIT: 13071098
 ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ /KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: FRI. MARCH 14/2014
 ACTION: BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-100 TENANT B-14 THE REAR DOOR DOES NOT LINE
 UP WITH THE SIDEWALK WHICH IS PART OF THE EXIT
 DISCHARGE ROUTE LEADING TO A PUBLIC WAY. 2010 FBC-B
 027.6 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL
 PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC
 WAY.
  
 2) A201 NOTE 34 HASHED LINES INDICATE FUTURE TENANT
 BUILD OUT ON THE FRONT FACADE. A302-2 IS A DETAIL
 INDICATING THIS AREA TO BE FINISHED WITH
 GRACE ICE AND WATER SHIED. PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR VERTICAL USE AND LIMITATIONS OF PRODUCT TO
 SUNLIGHT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED2010 FBC-B 1405.2 WEATHER PROTECTION. EXTERIOR
 WALLS SHALL PROVIDE WEATHER PROTECTION FOR THE
 BUILDING. THE MATERIALS OF THE MINIMUM NOMINAL
 THICKNESS SPECIFIED IN TABLE 1405.2 SHALL BE ACCEPTABLE
 AS APPROVED WEATHER COVERINGS.
  