| Plan Review Notes For Permit 14020322 |
| Permit Number |
14020322 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-11 14:02:31 | FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED | | | BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE | | | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. | | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 7.5 OF MECHANICAL EQUIPMENT. | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | |
|