| Plan Review Notes For Permit 14020315 |
| Permit Number |
14020315 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-03-18 09:45:33 | ****PROVISO**** | | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | ****ISSUED AT OWNER/BUILDER'S RISK**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SUBMIT INSTALLATION SCHEDULE AS A REVISION. | | | | | | INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING | | | ERRORS: | | | | | | SHUTTER MOUNTING CONNECTION TYPE STATES "ACCORDION" - | | | THIS IS THE SHUTTER TYPE. MOUNTING CONNECTION TYPE TO | | | CORRELATE WITH PRODUCT APPROVAL ANCHOR CHARTS, SEE | | | SHEET 11 (C1 - C5). | | | | | | SHUTTER GLASS SEPARATION COLUMN NOT COMPLETED | | | | | | SHUTTER SPAN COLUMN NOT COMPLETED | | | | | | ANCHOR TYPE SPECIFIES "SIMPSON #14." PLEASE SPECIFY A | | | FASTENER WHICH CORRELATES WITH THE FASTENERS IN THE | | | ANCHOR CHART ON SHEET 11. | | | | | | 2. PLEASE NOTE THAT THE OWNER TAKES RESPONSIBILITY FOR | | | THIS JOB AND PLEASE REVIEW FLORIDA STATUTE 489.103. THE | | | RESUBMITTAL WAS SUBMITTED IN THE NAME OF JOSE MENDIETA, | | | 561-308-9823. IT IS NOT CLEAR WHO THIS IS IN RELATION | | | TO THE OWNER BUILDER. | | | | | | | | | | | | |
|