 1. SUBMIT INSTALLATION SCHEDULE AS A REVISION.
  
 INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING
 ERRORS:
  
 SHUTTER MOUNTING CONNECTION TYPE STATES "ACCORDION" -
 THIS IS THE SHUTTER TYPE. MOUNTING CONNECTION TYPE TO
 CORRELATE WITH PRODUCT APPROVAL ANCHOR CHARTS, SEE
 SHEET 11 (C1 - C5).
  
 SHUTTER GLASS SEPARATION COLUMN NOT COMPLETED
  
 SHUTTER SPAN COLUMN NOT COMPLETED
  
 ANCHOR TYPE SPECIFIES "SIMPSON #14." PLEASE SPECIFY A
 FASTENER WHICH CORRELATES WITH THE FASTENERS IN THE
 ANCHOR CHART ON SHEET 11.
  
 2. PLEASE NOTE THAT THE OWNER TAKES RESPONSIBILITY FOR
 THIS JOB AND PLEASE REVIEW FLORIDA STATUTE 489.103. THE
 RESUBMITTAL WAS SUBMITTED IN THE NAME OF JOSE MENDIETA,
 561-308-9823. IT IS NOT CLEAR WHO THIS IS IN RELATION
 TO THE OWNER BUILDER.
  
  
  
  